Permit NumberFIR18-00902
StatusFinaled
Name TKG PROTECTION SYSTEMS
Site Address 816 W BANNOCK ST Unit: STE 100B
Project NameGarro Building 2018 Restrooms
Customer Number 
ePlanReviewYes
Description
Remodel of restrooms on floors 1 and 4. This will require removal of existing fire alarm notification devices and then re-installing them in the same location. This work is associated with building permit BLD18-03949.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/24/20191/28/20191/28/2019APASS
DetailsJim Page
Final fire alarm inspection for area of work complete.

Can we try to schedule this at 7AM, so that we can activate the horn strobes before anyone is in the building? Phone #: ###-#### Inspection requested via web by John Lopez
INSP-Final Inspection1/24/20191/25/20191/24/2019PCANC
DetailsJim Page
Phone #: ###-#### >> Inspection requested via web by John Lopez Inspection cancelled from web by: John Lopez
INSP-Final Inspection1/18/20191/18/20191/18/2019PFAIL
DetailsJim Page
Doors in restroom stalls go to ceiling, need notification installed in restroom stalls to be code compliant.

Phone #: ###-#### Inspection requested via web by John Lopez