Permit Information
Permit NumberFIR19-00074
StatusFinaled
Name CRANE ALARM SERVICE
Site Address 6615 S FEDERAL WAY
Project NamePeterbilt Paint Booth Upgrade
Customer Number 
ePlanReviewYes
Description
Provide a fire sprinkler monitoring system. This work is associated with building permit BLD18-01396.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/19/20194/22/20194/22/2019PPASS
DetailsJim Page
Final fire alarm inspection complete.

We are requesting that the inspection be at 1:00. Please call half hour prior to inspection to confirm Phone #: ###-#### Inspection requested via web by Heather Stier
INSP-Final Inspection4/19/20194/19/20194/19/2019PCANC
DetailsJim Page
Please call a half hour before appointment to confirm. We would like our inspection done at 1:00pm Phone #: ###-#### >> Inspection requested via web by Heather Stier Inspection cancelled from web by: Heather Stier
INSP-Final Inspection4/16/20194/17/20194/17/2019AFAIL
DetailsJim Page
Per alarm matrix on city approved drawings, paint booth is to be disabled during a general fire alarm, panit booth did not disable, panit prep room did. Provide knox box per note 12 of review comments. Fire sprinkler associated components have been tested and passed.



Confirm inspection 208.466.0613 Phone #: ###-#### Inspection requested via web by Cheyenne Zumstein