Permit Information
Permit NumberFIR19-00116
StatusFinaled
Name WEBSTER FIRE PROTECTION
Site Address 7805 W GRATZ DR
Project NameLyle Pearson Volvo
Customer Number 
ePlanReviewYes
Description
Addition of monitor module for existing RTU-8 located in living room area. This work is associated with building permit BLD17-04568..
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/27/20193/28/20193/28/2019APASS
DetailsTroy Cobbley
Permit finaled

Phone #: ###-#### Inspection requested via web by Ken Webster
INSP-Final Inspection3/18/20193/19/20193/19/2019ANR
DetailsTroy Cobbley
I arrived and found that the existing fire alarm panel has been replaced apparently without permits by another contractor. So no testing was performed. Phone #: ###-#### Inspection requested via web by Ken Webster
INSP-Final Inspection2/25/20192/25/20192/25/2019PFAIL
DetailsJim Page
Could not verify unit shutdown after initial smoke detector test, HVAC unit appears to be de-energized. Fire alarm panel has numorous issues, panel is showing a trouble with random characters showing up on screen, panel will not annunciate with troubles or supervisory signals. Monitoring was not verified during inspection.

Tom Phone #: ###-####