Permit Information
Permit NumberFIR19-00170
StatusFinaled
Name TRIBAL FIRE SYSTEMS
Site Address 1702 N MOCKBEE PL
Project NameMajors House
Customer Number 
ePlanReviewYes
Description
Fire Suppression system for a single family dwelling in the north end.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/11/201912/12/201912/12/2019PPASS
DetailsJim Page
Previously noted items have been corrected, storage area that did not have fire sprinkler head located under the stairs was blocked off and not accessible at time of inspection. No sprinkler timer or irrigation solenoids have been installed at time of inspection and I could not confirm with the homeowner when the landscaping will be installed. Any and all irrigation that is part of the domestic water system (treated metered water) needs to isolate and shut off during water flow switch activation, as noted this was not installed at time of inspection and will be required when landscaping irrigation is installed. Final fire sprinkler inspection complete.

Please call Chris ford Phone #: ###-#### Inspection requested via web by Jessia Maxwell
INSP-Final Inspection12/9/201912/10/201912/10/2019PFAIL
DetailsJim Page
Provide annual inspection for fire sprinkler backflow. Heads in apartment unit level 1 need heads raised so escutcheon covers entire hole. Add fire sprinkler in storage area under stairs on level 2 or make area under stairs not accessible.

Please call Jess before going out.

Thank you Phone #: ###-#### Inspection requested via web by Jessia Maxwell
INSP-Sprinkler Rough-in3/27/20193/27/20193/27/2019PPASS
DetailsJim Page
All tenting for overhead fire sprinkler piping in place at time of inspection, overhead fire sprinkler piping approved for cover. Noted that garage needs to be conditioned, garage needs to be maintained at 40 degrees or above to be code compliant.

Please call Clarence. This is an insulation inspection.

Thank you Phone #: ###-#### Inspection requested via web by Chris Gregory
INSP-Sprinkler Rough-in/Hydro3/15/20193/18/20193/18/2019APART
DetailsJim Page
Rough in inspection for overhead fire sprinkler piping complete, piping between conditioned spaces approved for cover, piping in attic spaces that requires tenting not approved for cover until tenting install is inspected and passed.

please call andre Phone #: ###-#### Inspection requested via web by Chris Gregory
INSP-Sprinkler Rough-in3/13/20193/15/20193/15/2019AFAIL
DetailsJim Page
Tenting above pipe on the level 3 east end will not meet the minimum R38 requirements for tenting, piping will need to be lowered/adjusted to meet thr R38 requirements.

please call Andre Phone #: ###-#### Inspection requested via web by Chris Gregory