Description |
This scope of work is to relocate two speaker/strobes and add additional audible devices to accommodate a tenant improvement in Unit 100 on the 1st floor of the Jefferson Building. The existing voice evac system is being modified, but no initiating devices are being affected by this T.I. Visual devices will be connected to existing FACP NAC #3, and the Audible devices will be connected to the existing AMP speaker circuit #3. Visual device candela ratings have been adjusted for ceiling heights over 10'. All ceilings are less than 20' in height. This work is associated with building permit BLD18-04004.
|