Information based on query as of Tuesday, June 18, 2024.
Permit Information
Permit NumberFIR19-00934
StatusFinaled
Name JOHNSON CONTROLS FIRE PROTECTION
Site Address 150 N 8TH ST
Project NameCapital Terrace Taphouse Speak
Customer Number 
ePlanReviewYes
Description
Capital Terrace Taphouse Speaker- MODIFY EXISTING FIRE ALARM SYSTEM: THE SCOPE OF WORK FOR THIS PROJECT IS TO REMOVE ALL EXISTING NOTIFICATION DEVICES WITHIN THE
TENANT SPACE & INSTALL NEW NOTIFICATION DEVICES AS NOTED ON PLANS.
THE NEW SPEAKER WIRING TO BE CLASS A AND VISUAL CIRCUIT TO BE CLASS B.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/31/20204/1/20204/1/2020APASS
DetailsJim Page
Previously noted items have been corrected, final inspection for this scope of work is complete.

Phone #: ###-#### Inspection requested via web by Kristin Dolan
INSP-Final Inspection1/31/20202/3/20202/3/2020AFAIL
DetailsJim Page
Speaker strobe in kitchen area is overspaced. A/V device wiring in seating area is attached to fire sprinkler piping, not allowed to attach to sprinkler piping per NFPA13. Three A/V devices in tenant space experience a double flash during active alarm, troubleshoot double flash issue and repair, A/V devices will be required to be activated during next inspection.

Brian Phone #: ###-####
INSP-Final Inspection1/28/20201/31/20201/31/2020AFAIL
DetailsJim Page
Inspection request was not coordinated with inspector, start time for inspector is 8AM unless approved by the fire section supervisor for a 7AM inspection time, as stated before on past inspections, 7AM inspection time needs to be coordinated with the inspector and approved by the fire section supervisor per notification to the fire section supervisor by the inspector.

Building is occupied - 7 am schedule Phone #: ###-#### Inspection requested via web by Kristin Dolan