Information based on query as of Tuesday, April 30, 2024.
Permit Information
Permit NumberFIR20-00063
StatusFinaled
Name THORPE FIRE SPRINKLER SYSTEMS
Site Address 7482 N LUCY ROSE LN
Project NameEAGLE HAWK APTS. BLD 3
Customer Number 
ePlanReviewYes
Description
TFSS TO INSTALL A NEW NFPA 13R FIRE SPRINKLER SYSTEM IN THIS NEW APARTMENT BUILDING.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/22/20206/22/20206/22/2020APASS
DetailsJim Page
Previously noted items have been corrected, final fire sprinkler inspection is complete.

Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Final Inspection6/17/20206/18/20206/18/2020PFAIL
DetailsJim Page
Replace 155 degree heads in washer/dryer closets to the 175 degree heads as shown on city approved drawings. Relocate overspaced head as discussed.

Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Supply line flush5/29/20206/1/20205/29/2020ACANC
DetailsJim Page
Scheduled for 9am with Stacy at Suez. Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
INSP-Sprinkler Rough-in/Hydro5/27/20205/27/20205/27/2020PCANC
DetailsJim Page
Underground hydro. Ready any time, call James before heading out. Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
INSP-Sprinkler Rough-in/Hydro4/8/20204/9/20204/9/2020PDONE
DetailsJim Page
Hydrostaic test for overhead fire sprinkler piping has been witnessed, no pressure loss observed at riser provided gauge.

Hydrostatic test Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Sprinkler Rough-in3/11/20203/12/20203/12/2020APASS
DetailsJim Page
All tenting in place at time of inspection, cover is approved, cover sticker placed on window.

Tenting inspection, call James with any concerns, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Sprinkler Rough-in3/11/20203/11/20203/11/2020PPART
DetailsJim Page
Rough in inspection complete, piping between conditioned spaces approved for cover. No tenting installed at time of inspection, piping requiring tenting not approved for cover.

Tenting and overhead rough, call James before heading out. Phone #: ###-#### Inspection requested via web by Anthony Minichiello