Permit Number | FIR20-00162 |
Status | Issued |
Name |
JOHNSON CONTROLS FIRE PROTECTION SE
|
Site Address |
3730 W QUAIL HOLLOW CT
|
Project Name | Quail Hollow Court |
Customer Number | |
ePlanReview | Yes |
Description |
**QUICK PERMIT** Quail Hollow Court - This is a remodel of an existing residence that was originally constructed with fire sprinklers in 2005. Originally there was an exterior porch area that was not protected. Adjacent to the porch was a corridor with two sprinklers. When the porch was remodeled it became an enclosed area and the corridor wall between the porch and the corridor went away. Now the heads in the corridor are over spaced to protect the remodeled area. This scope is to relocate the sprinklers to match the existing rooms on either side as shown on the plans. The spacing will be the same as the other two rooms. New sprinklers will be used of the same brand, type, and model as the rest of the residence. The remote area for this structure was at the top floor of the two story building. The work referenced takes place on the first floor. No hydraulic calculations have been created or submitted. This work involves moving two existing sprinklers less than 3 feet.
Residence, Two sprinklers total NFPA 13 D No hydraulic calculations Sprinkler head submittal
|