Final | 9/10/2018 | 9/11/2018 | 9/11/2018 | A | PASS |
Jack Reynolds
|
|
|
Please call tech if you need access/have questions: ###-#### Phone #: ###-#### Inspection requested via web by Melissa Skinner- RTU fuses ok- plumbing vents 10' away from fresh air intake- gas line supported- final ok
|
Final | 9/6/2018 | 9/7/2018 | 9/7/2018 | A | FAIL |
Jack Reynolds
|
|
|
Please call technician 30 minutes ahead of arriving onsite. ###-####. Phone #: ###-#### Inspection requested via web by Melissa Skinner- one rtu needs 50 amp fuses in disconnect- one rtu needs gas line supported - two rtu's in the center of the building have plumbing vents within 10' of the economizer
|
Mec-Aging Inspection | 9/3/2018 | 9/3/2018 | 9/4/2018 | | DONE |
Jack Reynolds
|
|
|
called total system services about this permit
|
Mec-Aging Inspection | 6/4/2018 | 6/4/2018 | 6/4/2018 | | CANC |
Chad Schwendiman
|
|
|
|