Permit Information
Permit NumberMEC18-00206
StatusFinaled
Name RM MECHANICAL
Site Address 3625 W ELDER ST
Project Name 
Customer NumberD17-003
ePlanReviewNo
Description
New: Furnish & install 117 PTAC units, 2 RTUs, 12 split heat pumps, 27 EFs, 18 electric
heaters, 116 exhaust terminal units, 1 dehumidifier, 2 MAUs, FSDs, GRDs, & ductwork
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/27/20186/27/20186/27/2018PPASS
DetailsJack Reynolds
Contact info: Jason Phone #: ###-#### Inspection requested via web by RM Mechanical
- p trap finished on rtu- linesets taped ok- exhaust fan 10' away from economizer- final ok- signed card
Final6/26/20186/27/20186/27/2018APART
DetailsJack Reynolds
Contact name: Jason Davidson Phone #: ###-#### Inspection requested via web by RM Mechanical- condensates on outside of building all have 90 turned down- all equipment room are finished- 2nd floor ptacs at end of hallway finished- need to finished insulation on roof- an rtu needs a p trap on condensate- and one exhaust fan is within 10' of an economizer, needs to be extended 10 ' away or 3' above
Final6/22/20186/22/20186/22/2018PPART
DetailsJack Reynolds
Contact Name: Jason Davidson Phone #: ###-#### Inspection requested via web by RM Mechanical- dryer vents ok- pool equipment room need to see ductless spilt finished- dehumid equipment condensate leaking- condensate on two ductless splits in laundry room need finished - all condensates on outside of building need terminated with an elbow down- will check roof on final inspection
Final6/15/20186/18/20186/18/2018APART
DetailsJack Reynolds
Contact Name: Jason Davidson Phone #: ###-#### Inspection requested via web by RM Mechanical- 1st floor east side mini splits condensates are supported
Final6/13/20186/13/20186/13/2018PPART
DetailsJack Reynolds
TCO - Contact Name: Jason Davidson Phone #: ###-#### Inspection requested via web by RM Mechanical- TCO ok- just a few things need to be finished at back of house, ptacs on 2nd floor corridors, condensate lines supported on east side, grilles on indoor ceiling mount ductless, access doors to equipment
Rough-in6/6/20186/7/20186/7/2018PPASS
DetailsJack Reynolds
Contact Name: Jason Davidson Phone #: ###-#### Inspection requested via web by RM Mechanical- 1st floor corridor and guest rooms ok- 4th floor corridor ok plans reviewed and ok- few back of house locations that still need some work like insulation finished, fire caulk penetrations at linesets, minisplit grilles installed
Rough-in5/23/20185/24/20185/24/2018ACANC
DetailsJack Reynolds
Contract Name: Jason Davidson Phone #: ###-#### Inspection requested via web by RM Mechanical- cancelled changes still under review
Rough-in5/21/20185/22/20185/22/2018PPART
DetailsJack Reynolds
Contact: Jason Davidson ###-#### Phone #: ###-#### Inspection requested via web by RM Mechanical- pool room exhaust duct ok for cover- 2nd floor corridors ok for ceiling cover- 2nd floor guest rooms ptacs ok- 3rd floor corridor ok for ceiling cover- 3rd floor guest rooms ptacs ok- 4th floor guest rooms ptacs ok-
Rough-in5/10/20185/11/20185/11/2018PPART
DetailsJack Reynolds
Contact Name: Jason Davidson Phone #: ###-#### Inspection requested via web by Melissa Kaae- 4th floor elev lobby ok to cover- 3rd floor elev lobby ok to cover- pool room from gridline 7-9 ok to cover still need to see tie in on south corner for exhaust duct going outside
Rough-in5/11/20185/11/20185/11/2018APART
DetailsJack Reynolds
pool room R/I from grid line 9 to grid line 12 ok for cover- Jason has a 5/11 pm Rough in scheduled for the rest of the pool room- gridline 9-12 ok for cover in pool room
Rough-in5/10/20185/11/20185/10/2018ACANC
DetailsJack Reynolds
Contact: Jason Davidson Phone #: ###-#### >> Inspection requested via web by Melissa Kaae Inspection cancelled from web by: Melissa Kaae
Rough-in5/10/20185/10/20185/10/2018APART
DetailsJack Reynolds
Contact Name: Jason Davidson - inspection for breakfast seating area Phone #: ###-#### Inspection requested via web by Melissa Kaae
- breakfast seating area ok to cover
Rough-in5/7/20185/8/20185/8/2018APART
DetailsJack Reynolds
Contact Name: Jason Davidson Phone #: ###-#### Inspection requested via web by Melissa Kaae- cover on first floor lobby east side ok
Rough-in5/4/20185/4/20185/4/2018PPASS
DetailsChad Schwendiman
Contact Name: Jason Davidson Phone #: ###-#### Inspection requested via web by Melissa Kaae - Fire/smoke dampers okay on 1st floor public bathrooms, framing around fire/smoke damper in lower ceiling of lobby okay
Rough-in4/26/20184/27/20184/27/2018APART
DetailsJack Reynolds
Requesting mechanical rough-in for tomorrow morning.

Contact: Jason Davidson Phone #: ###-#### Inspection requested via web by Melissa Kaae- partial cover for guest laundry dryer vent on 1st floor north side and one bathroom vent next to guest laundry 1st floor.
Rough-in4/9/20184/10/20184/10/2018APART
DetailsChad Schwendiman
Requesting Rough-In inspection for Tuesday AM.

Contact: Jason Davidson Phone #: ###-#### Inspection requested via web by Melissa Kaae - Fire damper installation and clearances okay on fire/smoke dampers in electrical rooms next to elevators, and fire/smoke damper in upper area of lobby. need framing and sheetrock around all 4 sides of fire/smoke damper in the lower area of the lobby. duct seaal okay on duct in corridoor on 3rd and 2nd floor. okay to cover bathroom ceiling in room 112. need to remove fire caulk from around fire dampers, and fire/smoke dampers
Rough-in3/28/20183/28/20183/28/2018PPART
DetailsChad Schwendiman
Rough in inspection request.

Contact: Jason Davidson Phone #: ###-#### Inspection requested via web by Melissa Kaae - Okay to cover bathroom ceilingd in rooms 101, 102, 103, 104, 105, 106, 107, 109, 111, 113, 115
Rough-in3/9/20183/12/20183/12/2018APART
DetailsChad Schwendiman
Request for Partial Rough-in Inspection

Contact: Jason Davidson Phone #: ###-#### Inspection requested via web by Melissa Kaae - Fire smoke damper okay on 1st floor behind elevator
Rough-in3/7/20183/8/20183/8/2018PPART
DetailsChad Schwendiman
Contact name: Jason Davidson Phone #: ###-#### Inspection requested via web by Melissa Kaae - Okay to cover bathroom ceilings on 2nd floor. Okay to cover mechanical shaft behind elevator on 2nd-4th floors
Rough-in3/6/20183/7/20183/7/2018AFAIL
DetailsChad Schwendiman
Contact Name: Jason Davidson Phone #: ###-#### Inspection requested via web by Melissa Kaae - Need installation instructions on site for Fire/smoke dampers
Rough-in2/22/20182/23/20182/23/2018PPART
DetailsChad Schwendiman
Phone #: ###-#### Inspection requested via web by Melissa Kaae - duct seal okay on west return shaft
Rough-in2/20/20182/21/20182/21/2018APART
DetailsChad Schwendiman
Contact Name: Jason Davidson Phone #: ###-#### Inspection requested via web by Melissa Kaae - 3rd floor bathroom ceilings in guest rooms okay to cover
Rough-in2/15/20182/16/20182/16/2018PPART
DetailsChad Schwendiman
Contact Name: Jason Davidson Phone #: ###-#### Inspection requested via web by Melissa Kaae - Return air shaft between 11, and 13 rooms okay to cover. will need framing around duct penetrations. okay to cover bathroom ceilings in rooms 301, 302, 303, 304, 305, 306, 308, 310. Corridoor ductwork for 4th floor has been changed and relocated from approved plans. Need to install per approved plans or resubmit new plans to City of Boise Plan Review for approval.
Rough-in2/8/20182/9/20182/9/2018PPASS
DetailsChad Schwendiman
Jason Phone #: ###-#### - Bathroom ceilings in the 4th floor okay to cover
Rough-in2/6/20182/7/20182/7/2018PPASS
DetailsChad Schwendiman
Jason Phone #: ###-#### - Okay to cover bathroom ceilings in rooms 401-112, and 414-421
Rough-in2/1/20182/2/20182/2/2018PPART
DetailsChad Schwendiman
Partial rough-in. Onsite contact: Jason Davidson. Phone #: ###-#### Inspection requested via web by Melissa Kaae - exhaust ducts in chases okay except for 7-9 chase, and 11-13 chase
Rough-in1/19/20181/22/20181/22/2018APASS
DetailsBen Livingston
contact name: Jason Davidson, inspection for 4th floor. Phone #: ###-#### Inspection requested via web by Melissa Kaae
4th floor restroom above cieling exhaust ok,
elevator lobby duct seal ok
Rough-in1/15/20181/16/20181/16/2018PPASS
DetailsChad Schwendiman
Contact name: Jason Davidson
rough-in for 4th floor Phone #: ###-#### Inspection requested via web by Melissa Kaae - Duct seal okay on duct work in attic for RTU-2
Conference1/15/20181/16/20181/15/2018PCANC
DetailsChad Schwendiman
Contact Name: Jason Davidson
rough in inspection for 4th floor Phone #: ###-#### >> Inspection requested via web by Melissa Kaae Inspection cancelled from web by: Melissa Kaae
Rough-in1/11/20181/12/20181/12/2018PPART
DetailsChad Schwendiman
Partial rough-in/cover for 4th floor. Onsite contact: Jason Davidson. Phone #: ###-#### Inspection requested via web by Melissa Kaae - okay to cover bottom of trusses in roms 402, 404, 406, 408, 410, 412, 414, 416, 418, 401, 403, 405