Permit Information
Permit NumberMEC18-01544
StatusFinaled
Name RM MECHANICAL
Site Address 8000 S FEDERAL WAY
Project NameC30616 B37 Office Building
Customer Number18-039
ePlanReviewNo
Description
New: FURNISH AND INSTALL HYDRONIC WATER SYSTEM AND NATURAL GAS.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final11/29/201811/30/201811/30/2018APASS
DetailsTroy James
Gas Final Phone #: ###-#### Inspection requested via web by RM Mechanical
Pressure Test11/21/201811/21/201811/21/2018PPASS
DetailsEric Strole
Gas Piping Rough In Phone #: ###-#### Inspection requested via web by RM Mechanical-60 lb gas test in penthouse pass.
Rough-in11/20/201811/21/201811/21/2018AFAIL
DetailsEric Strole
Gas Piping Rough In Phone #: ###-#### Inspection requested via web by RM Mechanical-Need to use a 100 lb gauge not a 200 lb gauge for a 60 lb test.
Rough-in11/14/201811/15/201811/15/2018APASS
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by RM Mechanical- 100# test on hydronics fitness area and fire riser room nw corner pass- ok for pipe insulation- initialed contractor print
Pressure Test9/24/20189/25/20189/25/2018APASS
DetailsTroy James
Hydronic air pressure test level one Phone #: ###-#### Inspection requested via web by RM Mechanical
1st floor hydroncis test
Pressure Test8/9/20188/10/20188/10/2018APASS
DetailsTroy James
Hydronic 2nd Floor Pressure Test Phone #: ###-#### Inspection requested via web by RM Mechanical
100# test
Pressure Test7/16/20187/17/20187/17/2018APASS
DetailsTroy James
Hydronic Pressure Test on Main Phone #: ###-#### Inspection requested via web by RM Mechanical
main from penthouse to first floor
Pressure Test7/12/20187/13/20187/13/2018APASS
DetailsTroy James
Hydronic pressure testing for insulating Hydronic Piping 3rd floor loop. Dennis White is the the Site Contact. Phone Number ###-####. Phone #: ###-#### Inspection requested via web by RM Mechanical
Ok 100# test to 3rd floor hydronics, ok to insulate
Pressure Test7/2/20187/3/20187/3/2018APART
DetailsTroy James
Partial Pressure Test on Gas Piping. Contact: Dennis Phone #: ###-#### Inspection requested via web by RM Mechanical
ok gas line from meter location to roof 68# test
Rough-in4/6/20184/9/20184/9/2018ANR
DetailsEric Strole
Requesting partial rough-in.

Contact: Dennis White Phone #: ###-#### Inspection requested via web by Melissa Kaae