Mec-Aging Inspection | 7/23/2019 | 7/23/2019 | 7/23/2019 | | PASS |
Jack Reynolds
|
|
|
Expired ok
|
DOC - Permit Expired | 7/23/2019 | 7/23/2019 | 7/23/2019 | A | PASS |
Jack Reynolds
|
|
|
Doc Permit Expired ok
|
Mec-Aging Inspection | 4/23/2019 | 4/23/2019 | 4/23/2019 | | DONE |
Jack Reynolds
|
|
|
called TVR and talked with Brandon about their mechanical aging permit. Add duct work to permit and reschedule. Permit will expire in 180 days if not active
|
Final | 9/18/2018 | 9/18/2018 | 9/18/2018 | P | FAIL |
Jack Reynolds
|
|
|
Final - call RJ 30 minutes before arrival Phone #: ###-#### Inspection requested via web by Brandon Sorensen- 20lb gas pressure test ok- wet switch ok- co detectors ok- lineset penetration ok- electrical conduit for A/C ok- - need to add other to permit for duct work in addition
|
Final | 9/4/2018 | 9/5/2018 | 9/5/2018 | A | FAIL |
Jack Reynolds
|
|
|
final - call RJ 1/2 hour before inspection so we can have someone on-site Phone #: ###-#### Inspection requested via web by Brandon Sorensen - need to see a 20lb gas pressure test on gas line- line set needs insulation installed through wall penetration and sealed- need to install wet switch on secoundary- home needs co detectors installed near bedrooms- electrical contractor needs to run weather tight conduit for A/C disconnect- add other to permit for new duct work
|