Rough-in | 10/1/2019 | 10/2/2019 | 10/2/2019 | A | PASS |
Ben Livingston
|
|
|
R/I inspection on room 406 range hood. Please call Curt at ###-#### prior to arrival on-site. Phone #: ###-#### Inspection requested via web by Commercial Coordinator
|
DOC - Permit Finaled | 10/2/2019 | 10/2/2019 | 10/2/2019 | P | PASS |
Ben Livingston
|
|
|
|
Final | 9/23/2019 | 9/24/2019 | 9/24/2019 | A | PART |
Chad Schwendiman
|
|
|
Afton 2 final inspection. Please call Curt at ###-#### prior to arrival on-site. Phone #: ###-#### Inspection requested via web by Commercial Coordinator - Temporary Occupancy okay except for unit 406. Still need to complete unit 406
|
Rough-in | 9/19/2019 | 9/23/2019 | 9/23/2019 | A | PASS |
Chad Schwendiman
|
|
|
Requesting an inspection on the parking garage ; roof. Please call Curt before coming out - ###-#### Phone #: ###-#### Inspection requested via web by Commercial Coordinator
|
Rough-in | 9/19/2019 | 9/20/2019 | 9/19/2019 | A | CANC |
Chad Schwendiman
|
|
|
Requesting an inspection on the parking garage ; roof. Please call Curt before coming out - ###-#### Phone #: ###-#### Inspection requested via web by Commercial Coordinator - I spoke with Curt and let him know I rescheduled this inspection for Monday
|
Rough-in | 9/12/2019 | 9/16/2019 | 9/16/2019 | P | PASS |
Chad Schwendiman
|
|
|
Final inspection for 5th floor. Contact Curt at ###-#### prior to arrival on-site. Phone #: ###-#### Inspection requested via web by Heather Gransbery
|
Rough-in | 9/10/2019 | 9/11/2019 | 9/11/2019 | A | PASS |
Ben Livingston
|
|
|
Final inspection for room #204, 1st floor lobby and 1st floor retail area. Contact Curt at ###-#### prior to arrival on-site Phone #: ###-#### Inspection requested via web by Heather Gransbery - room 204, 1st floor lobby, 1st floor retail space final okay -
|
Rough-in | 9/6/2019 | 9/9/2019 | 9/9/2019 | A | PASS |
Chad Schwendiman
|
|
|
Final inspection for 4th floor with the exception of room 406. Please contact Curt at ###-#### prior to arrival on-site. Phone #: ###-#### Inspection requested via web by Heather Gransbery
|
Rough-in | 8/21/2019 | 8/22/2019 | 8/22/2019 | P | PASS |
Chad Schwendiman
|
|
|
Requesting a inspection on fire dampers shaft walls in hallway. Please contact Curt before coming out ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery
|
Rough-in | 8/21/2019 | 8/22/2019 | 8/22/2019 | A | PASS |
Chad Schwendiman
|
|
|
Requesting a C/I for the 3rd floor hallway bathroom. Please contact Curt before coming out. 28-###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery
|
Rough-in | 8/21/2019 | 8/21/2019 | 8/21/2019 | P | NR |
Chad Schwendiman
|
|
|
Requesting an Inspection on fire damper shaft walls in hallway. Please contact Curt before coming out ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery
|
Rough-in | 8/20/2019 | 8/20/2019 | 8/20/2019 | P | FAIL |
Chad Schwendiman
|
|
|
Requesting an inspection for Tuesday afternoon. Fire fire dampers shaft walls in hallway. Please call Curt before coming out. ###-####. Phone #: ###-#### Inspection requested via web by Heather Gransbery - Need to remove sheetrock from face of shaft wall to verify framing around dampers
|
Rough-in | 8/12/2019 | 8/13/2019 | 8/13/2019 | A | PASS |
Chad Schwendiman
|
|
|
Inspection for trash chutes, call Curt ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery
|
Rough-in | 8/7/2019 | 8/8/2019 | 8/8/2019 | A | PASS |
Chad Schwendiman
|
|
|
R/I for 5th floor hallway - call Curt ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery
|
Rough-in | 8/5/2019 | 8/6/2019 | 8/6/2019 | A | PASS |
Chad Schwendiman
|
|
|
Inspection for dampers, shaft ; 5th floor hallway. Call Curt ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery
|
Rough-in | 7/31/2019 | 8/1/2019 | 8/1/2019 | A | PART |
Chad Schwendiman
|
|
|
Final for 3rd Floor , call Curt ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery - living units okay for 3rd floor except for 312.
|
Rough-in | 7/26/2019 | 7/29/2019 | 7/29/2019 | A | PASS |
Chad Schwendiman
|
|
|
Requesting a 2nd floor final inspection. Please call curt before coming out ###-#### Phone #: ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery - 2nd floor units okay except fpr unit 204
|
Rough-in | 7/25/2019 | 7/26/2019 | 7/26/2019 | A | FAIL |
Chad Schwendiman
|
|
|
Requesting a 2nd floor final inspection. Please call curt before coming out ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery - Need to remove covers from range vents to be able to inspect duct connection. Need to seal range vent connections that aren't sealed. Need access doors for equipment opened to view connections to equipment.
|
Rough-in | 7/22/2019 | 7/23/2019 | 7/23/2019 | A | PASS |
Chad Schwendiman
|
|
|
Requesting an Inspection for the Mechanical Room, R/I First Floor ; Trash Chutes. Please call Curt before coming out ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery
|
Rough-in | 7/17/2019 | 7/18/2019 | 7/18/2019 | A | PART |
Chad Schwendiman
|
|
|
Requesting a R/I inspection for the mechanical room and pump riser room. Please contact Curt before coming out. ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery - Need to trim sheetrock back to get expansion clearances, need to sheetrock framing between fire/smoke dampers on garage exhaust
|
Rough-in | 7/16/2019 | 7/17/2019 | 7/17/2019 | A | CANC |
Chad Schwendiman
|
|
|
Requesting a R/I inspection for the mechanical room and pump riser room. Please contact Curt before coming out. ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery - rescheduled for tomorrow
|
Rough-in | 7/16/2019 | 7/16/2019 | 7/16/2019 | P | PASS |
Chad Schwendiman
|
|
|
Requesting a R/I inspection for north end, 5th floor hall. Please call Curt before coming out - ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery
|
Rough-in | 7/10/2019 | 7/11/2019 | 7/11/2019 | A | PASS |
Chad Schwendiman
|
|
|
Requesting a R/I inspection on #506. Please call Curt before coming out ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery
|
Rough-in | 6/4/2019 | 6/5/2019 | 6/5/2019 | A | PASS |
Chad Schwendiman
|
|
|
Requesting a trash chute Inspection and A final inspection on townhouses # 201, 202, 203. Please call Curt before coming out @ ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery - Duct seal on trash chute duct okay. units 201-203 okay
|
Rough-in | 6/3/2019 | 6/4/2019 | 6/4/2019 | A | PART |
Chad Schwendiman
|
|
|
R/I Inspection for Room 406 ; Trash Chute. Please call Curt @ ###-#### before coming out. Phone #: ###-#### Inspection requested via web by Heather Gransbery - 406 pass, trash chute duct fail, need to seal back side of ductwork
|
Rough-in | 5/29/2019 | 5/30/2019 | 5/30/2019 | A | PASS |
Troy James
|
|
|
R/I inspection for the 4th floor hall. Please call curt before coming out at ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery
|
Rough-in | 5/28/2019 | 5/29/2019 | 5/29/2019 | A | PASS |
Troy James
|
|
|
R/I for rooms 507, 509 - call Curt ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery
|
Rough-in | 5/23/2019 | 5/23/2019 | 5/23/2019 | P | PASS |
Ben Livingston
|
|
|
We would like to request a R/I inspection for room 506. Please call Curt before coming out ###-####. Phone #: ###-#### Inspection requested via web by Heather Gransbery 506 prerock okay
|
Rough-in | 5/21/2019 | 5/21/2019 | 5/21/2019 | P | PASS |
Chad Schwendiman
|
|
|
3rd floor hall R/I final and 2nd floor amenities R/I final. Please call Curt prior to coming out at ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery - Okay to cover 3rd floor hallway
|
Rough-in | 5/20/2019 | 5/21/2019 | 5/21/2019 | A | FAIL |
Chad Schwendiman
|
|
|
3rd floor hall R/I final and 2nd floor amenities R/I final. Please call Curt prior to coming out at ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery - Corrections not fixed
|
Final | 5/20/2019 | 5/20/2019 | 5/20/2019 | P | CANC |
Chad Schwendiman
|
|
|
3rd floor hall R/I final ; 2nd floor Amenities R/I final. Please call Curt prior to coming out at ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery - this should have been scheduled as a rough in. I entered one for it
|
Rough-in | 5/20/2019 | 5/20/2019 | 5/20/2019 | P | PASS |
Chad Schwendiman
|
|
|
3rd floor hall R/I final ; 2nd floor Amenities R/I final. Please call Curt prior to coming out at ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery - 2nd floor amenities room 204 okay to cover. 3rd floor hall fail. Need to angle around fire damper above doorway per manufactures instructions.
|
Rough-in | 5/13/2019 | 5/14/2019 | 5/14/2019 | A | PART |
Chad Schwendiman
|
|
|
Rough Cover units 511-515 // Call Curt ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery - 512, 514, 515 okay to cover. 511, and 513 exhaust air needs to terminate 10' away or 3' above fresh air intake
|
Rough-in | 5/3/2019 | 5/6/2019 | 5/6/2019 | A | PASS |
Chad Schwendiman
|
|
|
Inspection for 2nd floor hall. Please contact Curt Miller at ###-#### prior to arrival on-site. Phone #: ###-#### Inspection requested via web by Heather Gransbery - Okay to cover 2nd floor hallway
|
Rough-in | 4/17/2019 | 4/18/2019 | 4/18/2019 | A | PASS |
Chad Schwendiman
|
|
|
Rough Cover for 407, call Curt Miller ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery
|
Rough-in | 4/16/2019 | 4/17/2019 | 4/17/2019 | P | PART |
Chad Schwendiman
|
|
|
Rough cover for units 407 ; 409. Call Curt Miller ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery - 409 okay to cover. 407 needs condensate completed
|
Rough-in | 4/12/2019 | 4/15/2019 | 4/15/2019 | A | PASS |
Chad Schwendiman
|
|
|
Request for final rough cover units 411 412 413 414 415 Request for rough cover unit 507 Inspection requested via web by Heather Gransbery
|
Rough-in | 4/11/2019 | 4/12/2019 | 4/12/2019 | A | PASS |
Chad Schwendiman
|
|
|
3rd floor conference room rough cover, 6th floor penthouse rough cover, 2nd floor amenities rough cover. Please call Curt Miller ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery
|
Rough-in | 4/8/2019 | 4/8/2019 | 4/8/2019 | P | PASS |
Chad Schwendiman
|
|
|
Final rough cover for #306, inspect trash chute exhaust on roof. Call Curt ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery - unit 306 okay to cover. duct seal okay on trash shoot exhaust on roof
|
Rough-in | 4/8/2019 | 4/8/2019 | 4/8/2019 | P | CANC |
Chad Schwendiman
|
|
|
Final rough cover for #206, inspect trash chute exhaust on roof. Call Curt ###-####. Phone #: ###-#### >> Inspection requested via web by Heather Gransbery Inspection cancelled from web by: Heather Gransbery
|
Rough-in | 4/4/2019 | 4/8/2019 | 4/8/2019 | A | PART |
Chad Schwendiman
|
|
|
We would like to request s final rough cover for rooms 306, 307, 312. Please call Curt at ###-#### before coming out. Phone #: ###-#### Inspection requested via web by Heather Gransbery - Okay to cover units 307, and 312. Need to fix trapped condensate on unit 306
|
Rough-in | 4/2/2019 | 4/3/2019 | 4/3/2019 | A | PASS |
Chad Schwendiman
|
|
|
We are requesting a rough cover inspection for tomorrow morning, April 3rd for #206. Please call Curt at ###-#### before coming out. Phone #: ###-#### Inspection requested via web by Heather Gransbery - Unit 206 okay to cover
|
Rough-in | 4/1/2019 | 4/2/2019 | 4/2/2019 | A | PART |
Chad Schwendiman
|
|
|
We are requesting a re-inspection for tomorrow morning, April 2nd at the Afton Phase 2 for rooms 206 and 207. We are also requesting a rough cover inspection for tomorrow morning, April 2nd for rooms 309,311,313,315. Please call Kurt at ###-#### before coming out. Phone #: ###-#### Inspection requested via web by Heather Gransbery - Unit 207, 309, 311, 113, 114, 115 okay to cover. unit 206 fail Need exhaust termination needs to be 10' away or 3" above fresh air intake
|
Rough-in | 3/28/2019 | 4/1/2019 | 4/1/2019 | A | NR |
Chad Schwendiman
|
|
|
Final Rough for units 206 ; 207. Call Curt ###-####. Phone #: ###-#### Inspection requested via web by Heather Gransbery
|
Rough-in | 3/28/2019 | 3/29/2019 | 3/28/2019 | A | CANC |
Chad Schwendiman
|
|
|
Rough Final for units 206-207. Call Curt Miller ###-#### Phone #: ###-#### >> Inspection requested via web by Heather Gransbery Inspection cancelled from web by: Heather Gransbery
|
Rough-in | 3/26/2019 | 3/26/2019 | 3/26/2019 | P | PASS |
Chad Schwendiman
|
|
|
Rough Cover 209 - Call Curt ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery - Okay to cover 209
|
Rough-in | 3/12/2019 | 3/14/2019 | 3/14/2019 | A | PASS |
Ben Livingston
|
|
|
Rough Cover for units 211-215 - please call Curt Miller ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery
|
Rough-in | 2/28/2019 | 3/1/2019 | 3/1/2019 | A | PASS |
Ben Livingston
|
|
|
Request for R/I cover inspection 4th and 5th floors, excluding rooms 506;507 Please contact job lead Curt ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery
|
Rough-in | 1/31/2019 | 2/1/2019 | 2/1/2019 | A | PART |
Ben Livingston
|
|
|
Rough wall cover for units 206 207 306 307, please call Curt with any questions ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery pre rock rough-in okay
|
Rough-in | 1/29/2019 | 1/29/2019 | 1/29/2019 | P | PART |
Ben Livingston
|
|
|
Rough cover for town-homes 201, 202 and 203 - 2nd floor only. Please call Curt Miller ###-####. Phone #: ###-#### Inspection requested via web by Heather Gransbery 201,202,203 1st and 2nd floor okay
|
Rough-in | 1/25/2019 | 1/25/2019 | 1/25/2019 | P | PART |
Troy James
|
|
|
Reinspection for units 209, 309, 315. Please call Curt ###-####. Phone #: ###-#### Inspection requested via web by Heather Gransbery Okay condensate drains units 209,309,315
|
Rough-in | 1/22/2019 | 1/23/2019 | 1/23/2019 | A | PART |
Ben Livingston
|
|
|
Rough cover for units 209, 211, 212, 213, 214, 215, 309, 311, 312, 313, 314, 315. Please call Curt ###-####. Phone #: ###-#### Inspection requested via web by Heather Gransbery 211-214, 311-314 okay pre rock 209,309,315 still need condensates run, fail
|
Rough-in | 1/10/2019 | 1/11/2019 | 1/11/2019 | A | FAIL |
Ben Livingston
|
|
|
Rough cover for units 209, 211, 212, 213, 214, 215, 309, 311, 312, 313, 314, 315. Please call Curt ###-####. Phone #: ###-#### Inspection requested via web by Heather Gransbery condensate piping not run, firesmoke damper on exhaust fan in parking garage blades arent in the wall.
|
Rough-in | 12/20/2018 | 12/21/2018 | 12/21/2018 | A | FAIL |
Chad Schwendiman
|
|
|
Rough cover for 2nd level. Please call Curt ###-####. Phone #: ###-#### Inspection requested via web by Heather Gransbery - Still no approved plans onsite
|
Rough-in | 12/11/2018 | 12/12/2018 | 12/11/2018 | A | CANC |
Chad Schwendiman
|
|
|
Partial Rough Cover for level 2 condominiums, please call Curt with any questions ###-#### Phone #: ###-#### >> Inspection requested via web by Heather Gransbery Inspection cancelled from web by: Heather Gransbery
|
Rough-in | 12/10/2018 | 12/11/2018 | 12/11/2018 | A | FAIL |
Chad Schwendiman
|
|
|
Partial Rough Cover for level 2 condominiums, please call Curt with any questions ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery - Still no approved plans onsite
|
Rough-in | 11/27/2018 | 11/28/2018 | 11/28/2018 | A | PART |
Troy James
|
|
|
R/I for Afton 2, please call Curt Miller ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbrey ok the dryer duct in 6" wall at second level condos per previous correction
|
Rough-in | 11/19/2018 | 11/20/2018 | 11/20/2018 | A | FAIL |
Chad Schwendiman
|
|
|
Request for R/I cover inspection on townhomes. Please contact job lead, Curt, with any questions or concerns ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery - Need to fur out wall with dryer duct in it to a minimum of 4"
|