Permit Information
Permit NumberMEC18-05338
StatusFinaled
Name DEBEST PLUMBING INC
Site Address 12251 W FRANKLIN RD
Project Name 
Customer Number18-74
ePlanReviewNo
Description
New: natural gas piping to RTU''s and unit heaters.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/18/20197/18/20197/18/2019PPASS
DetailsBrian Scoles
final ok- card signed
Final5/31/20196/3/20196/3/2019PPART
DetailsBrian Scoles
if questions call Mike C. @ ###-#### Phone #: ###-#### Inspection requested via web by Stacia Haumann- gas piping after shutoff valve to unit heater 6 needs extended down has conflict with fkue vent, flue vent needs grade to outside and gas line is pushing it up- need to seal weather tight exterior penetration at meter location- went over onsite with installer- will final this permit out when other Mech contractor inspection is completed- Rest is good
Pressure Test5/22/20195/22/20195/22/2019APART
DetailsBrian Scoles
call mike with questions 208 ###-#### Inspection requested via web by Stacia Haumann- 60lb gas pass from meter to roof- will need to see 20lb test after regulators thru roof to unit heaters- will needs secure piping on roof to roof blocks and install condensate drains on RTUs by final
Pressure Test5/20/20195/21/20195/21/2019AFAIL
DetailsBrian Scoles
if questions call Mike C. @ ###-#### Phone #: ###-#### Inspection requested via web by Stacia Haumann- 60lb gas test needs to have max 100lb gauge- would like temp shut off valve installed between gauge and gas piping for pressure test