Final | 1/2/2019 | 1/3/2019 | 1/3/2019 | P | PASS |
Brian Scoles
|
|
|
Contact Dave Dixon at the number above if you have any questions. Phone #: ###-#### Inspection requested via web by David Dixon
|
Pressure Test | 12/28/2018 | 12/28/2018 | 12/28/2018 | P | PASS |
Brian Scoles
|
|
|
The inspector has already been given permission by owner to enter the garage to whiteness the test. Contact the contractor Greg Bouwer at ###-#### for any questions about gaining entrance. Phone #: ###-#### Inspection requested via web by David Dixon- 60lb gas pass- tagged gas line at meter bar- will need to see drip leg after shut off valve but before regulator and need to secure csst above unit heater flue vent with 6" clearance to csst by final- call in final when ready
|
Pressure Test | 12/11/2018 | 12/12/2018 | 12/12/2018 | A | FAIL |
Brian Scoles
|
|
|
Please contact the contractor Greg Bauer at ###-#### when your on your way so he can meet you there. Phone #: ###-#### Inspection requested via web by David Dixon- 2lb gas test needs 100 pound gauge max with 60lb test on line- need drip leg after shut off valve before regulator on unit heater-
|
Pressure Test | 12/10/2018 | 12/11/2018 | 12/11/2018 | P | NH |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by David Dixon- no one home- can not enter residence with out homeowner or contractor present-
|