Final | 2/8/2019 | 2/8/2019 | 2/8/2019 | P | PASS |
Brian Scoles
|
|
|
made corrections and sent photos of bubble wrap that is now double wrapped to have proper insulation. Please call me if any issues, my name is Steve Dale Phone #: ###-#### Inspection requested via web by Rick Montgomery
|
Final | 1/30/2019 | 1/31/2019 | 1/31/2019 | A | FAIL |
Brian Scoles
|
|
|
PLEASE CALL STERLING WHEN 30 MINS IN ROUTE Phone #: ###-#### Inspection requested via web by Rick Montgomery- furnace a/c coil co ok- bubble wrap insulation needs 3/4" air gap per installation instructions to maintain R-6 value whats installed on meets R-4.2- talked with steve about this by phone
|