Information based on query as of Sunday, May 12, 2024.
Permit Information
Permit NumberMEC19-00989
StatusFinaled
Name ALLEY HEATING & COOLING
Site Address 2120 N WOODCREEK ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete HVAC Installation: FURNACE, DUCT WORK, FIRE PLACE, GAS PIPING, A/C, BATH VENT, KITCHEN VENT
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/29/20195/29/20195/29/2019PPASS
DetailsBrian Scoles
GARAGE CODE 3484 Phone #: ###-#### Inspection requested via web by Oleg Chervak- fireplace and hvac final ok
Final5/21/20195/24/20195/24/2019PFAIL
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Oleg Chervak- no air balance report, approved man j or duct blast has been done- line set needs tied into coil- reschedule when completed
Rough-in3/20/20193/20/20193/20/2019PPASS
DetailsBrian Scoles
HVAC R/I and fireplace R/I ok
Pressure Test3/20/20193/20/20193/20/2019PPASS
DetailsBrian Scoles
20lb gas pass- tagged meter location- 5lb flue test pass
Rough-in3/19/20193/20/20193/20/2019AFAIL
DetailsBrian Scoles
RE-INSPECTION, REQUEST 11AM Phone #: ###-#### Inspection requested via web by Oleg Chervak- flue wasnt under test- all corrections not made
Rough-in3/15/20193/15/20193/15/2019PFAIL
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Oleg Chervak- need flue under test/gas test fail under 20psi- need to insulate supply and R/A ducts in joist above furnace- need to seal inside all boots 2nd floor supply and return- fireplace installation instructions need to easily accessed its behind glass- insulation on wye branch 2nd floor at stairs needs vapor barrier on it exposed insulation- need to secure b vent for water heater in chase and attic 2nd floor-need to seal dryer duct where enters termination box- left correction notice front entry window
Pressure Test3/15/20193/15/20193/15/2019PFAIL
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Oleg Chervak- need flue under test/ gas test failed gauge below 20psi