Final | 5/28/2019 | 5/28/2019 | 5/28/2019 | A | PASS |
Brian Scoles
|
|
|
meet at 1130- duct blast witnes and final- duct blast test pass- final ok
|
Final | 5/23/2019 | 5/24/2019 | 5/24/2019 | A | FAIL |
Brian Scoles
|
|
|
lift up garage door it is unlocked Phone #: ###-#### Inspection requested via web by Terek Worley- water heater flue not addressed in correction- still no duct blast done- need to schedule duct if your doing test or 3rd party
|
Final | 5/15/2019 | 5/15/2019 | 5/15/2019 | P | FAIL |
Brian Scoles
|
|
|
garage code 1234 Phone #: ###-#### Inspection requested via web by Terek Worley- need duct blast test completed and if done by integrity will need to be witneesed- water heater flue needs to be ran in all single wall or b vent can not go from b vent at china cap to single wall back to b vent
|
Rough-in | 3/25/2019 | 3/25/2019 | 3/25/2019 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Terek Worley- R/I ok
|
Rough-in | 3/21/2019 | 3/22/2019 | 3/22/2019 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Terek Worley- need city approved and stamped manual J onsite- outside air can not tie into R/A can needs tied into plenum- contractor needs to provide ladder to access furnace and coil in attic- left notice front window
|
Pressure Test | 3/21/2019 | 3/22/2019 | 3/22/2019 | A | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Terek Worley- 20lb gas pass- tagged meter location
|