Final | 5/22/2019 | 5/22/2019 | 5/22/2019 | P | PASS |
Brian Scoles
|
|
|
Bj 5730755 Inspection requested via web by william kerwin- final ok- card signed- engineer approved RTUs installed
|
Final | 5/8/2019 | 5/8/2019 | 5/8/2019 | P | PART |
Brian Scoles
|
|
|
After 1 if possible. Need ceiling cover inspection. Rtus are equivalent to whats speced.will send over to engineers for review. Inspection requested via web by william kerwin- ok to cover with ceiling tiles- final will pass when engineer approves RTUs installed
|
Final | 5/8/2019 | 5/8/2019 | 5/8/2019 | A | FAIL |
Brian Scoles
|
|
|
Bj 573 0755 Inspection requested via web by william kerwin 1- need to seal gas line penetrations exterior of builiding at meter location 2- need to insulate wye branches above ceiling in SW corner bare metal showing 3- RTU dont match approved drawings for manufacture or sizing- needs to get engineer approval for whats installed 4- waiting room supply needs rerouted will be pinched off when ceiling tiles are installed
left correction notice front entry window
|
Pressure Test | 3/25/2019 | 3/25/2019 | 3/25/2019 | A | PASS |
Brian Scoles
|
|
|
After 10 if possible. Thanks bj Inspection requested via web by william kerwin- 60lb gas pass- tagged meter location
|
Rough-in | 3/25/2019 | 3/25/2019 | 3/25/2019 | A | PASS |
Brian Scoles
|
|
|
After 10 if possible. Thanks bj Inspection requested via web by william kerwin- R/I ok- ok for grid- need to complete insulation on wye branches sw corner by final
|
Rough-in | 3/21/2019 | 3/22/2019 | 3/22/2019 | P | PART |
Brian Scoles
|
|
|
Permit had been issued but in Review status for Plan mod, adding kitchen appliances- please call Permit desk for any questions. Please call Adam for access Phone #: ###-####- R/I will pass when gas test passes- R/A and supply drops both units need flex connectors installed per general note 13-
|
Pressure Test | 3/21/2019 | 3/22/2019 | 3/22/2019 | A | FAIL |
Brian Scoles
|
|
|
Permit had been issued but in Review status for Plan mod, adding kitchen appliances- please call Permit desk for any questions. Please call Adam for access Phone #: ###-####- gauge at 18 psi
|
Pressure Test | 3/20/2019 | 3/20/2019 | 3/20/2019 | P | CANC |
Brian Scoles
|
|
|
Bj 2085730755. Wall cover /rough in inspection Inspection requested via web by william kerwin
|
Rough-in | 3/20/2019 | 3/20/2019 | 3/20/2019 | P | CANC |
Brian Scoles
|
|
|
Bj 2085730755. Wall cover /rough in inspection Inspection requested via web by william kerwin- bld permit needs issed to do inspection-
|