Final | 5/16/2019 | 5/17/2019 | 5/17/2019 | A | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Randy Hart- final ok
|
Final | 5/15/2019 | 5/16/2019 | 5/16/2019 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Randy Hart- need air balance report onsite
|
Rough-in | 3/29/2019 | 4/1/2019 | 4/1/2019 | P | PASS |
Brian Scoles
|
|
|
re inspection Phone #: ###-#### Inspection requested via web by Randy Hart- R/I ok- need to secure flue in attic by final no supports
|
Pressure Test | 3/29/2019 | 4/1/2019 | 4/1/2019 | P | PASS |
Brian Scoles
|
|
|
re inspection Phone #: ###-#### Inspection requested via web by Randy Hart- 20lb gas pass- tagged meter location
|
Rough-in | 3/28/2019 | 3/29/2019 | 3/29/2019 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Randy Hart- 1- fireplace instructions on inside of glass need to be readily accessible 2- all supply and R/A registers need to be sealed with mastic 3- need ladder provided by contractor to access furnace/coil in attic 4- all exhaust fan connections need sealed where metal duct ties on to plastic fan housing under flex 5- ducting pinched off in attic above master bath needs to flow smoothly on 2 supply runs 6- need nail plate flor and ceiling both sides of framing on condensate drain 2nd floor and ceiling 1st floor 7- range ducting needs tape sealed to pipe has gaps 8- gas test fail at 14psi 9- b vent in garage between joists needs 1" clearance
left correction notice front living room window on inside
|
Pressure Test | 3/28/2019 | 3/29/2019 | 3/29/2019 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Randy Hart- gauge at 14psi
|