Information based on query as of Sunday, May 12, 2024.
Permit Information
Permit NumberMEC19-02354
StatusFinaled
Name CUSTOM HEATING AND AIR CONDITIONING
Site Address 5835 W TARGEE ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration or Repair: replace furnace ac evaporator coil and add 5 supply runs to new addition
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final8/20/20198/20/20198/20/2019APASS
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Dave Sorensen
Rough-in6/14/20196/14/20196/14/2019PPASS
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Dave Sorensen- R/I ok- will need air balance on new supply ducting at final- condenser needs rotated 90 degrees from regulator on gas line to maintain 3 feet clearance and weather tight whip needs installed from disconnect to condenser by final
Final6/13/20196/13/20196/13/2019PCANC
DetailsChad Schwendiman
please call dave prior to arrival Phone #: ###-#### Inspection requested via web by Dave Sorensen
Rough-in6/5/20196/6/20196/6/2019AFAIL
DetailsBrian Scoles
flue pressure test and rough in. call Tracy 30 min prior to arrival @ 208 -###-#### for access to job site Phone #: ###-#### Inspection requested via web by Dave Sorensen- need to submit manual J to city for approval and have approved copy onsite for inspection
Pressure Test6/6/20196/6/20196/6/2019APASS
DetailsBrian Scoles
flue pressure test and rough in. call Tracy 30 min prior to arrival @ 208 -###-#### for access to job site Phone #: ###-#### Inspection requested via web by Dave Sorensen- 5lb flue test pass