Final | 1/8/2020 | 1/9/2020 | 1/9/2020 | P | PASS |
Brian Scoles
|
|
|
AC:2019 Phone #: ###-#### Inspection requested via web by Gary Reeves- final ok
|
Rough-in | 10/18/2019 | 10/18/2019 | 10/18/2019 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves- R/I ok
|
Pressure Test | 10/18/2019 | 10/18/2019 | 10/18/2019 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves
|
Rough-in | 10/16/2019 | 10/17/2019 | 10/17/2019 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves- 1- need inert tape on gas line 2- need approved man j onsite 3- exhaust fan 2nd floor has trap in 4" duct needs to maintain grade from fan to roof 4- dryer duct can not run in 2x4 wall needs firred out or rerouted 5- ducting in crawl needs to maintain 4" off earth and bare metal needs insulated at zone damper
left correction notice front window
|
Pressure Test | 10/16/2019 | 10/17/2019 | 10/17/2019 | P | PART |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves- 20lb gas pass tagged meter location- need inert tape on gas line penetration thru wall at meter location
|