Final | 4/26/2020 | 4/27/2020 | 4/27/2020 | A | PASS |
Jack Reynolds
|
|
|
Garage code 5513 Phone #: ###-#### Inspection requested via web by santiago ramirez - final ok
|
Final | 4/24/2020 | 4/24/2020 | 4/24/2020 | P | FAIL |
Jack Reynolds
|
|
|
Keys are indide electrical box by the front door Phone #: ###-#### Inspection requested via web by santiago ramirez - gas line penetartion needs sealed - fresh air duct in garage needs insulated
|
Rough-in | 2/5/2020 | 2/5/2020 | 2/5/2020 | P | PASS |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by santiago ramirez - 20lb gas pressure test ok - tagged meter location - R/I
|
Rough-in | 2/4/2020 | 2/5/2020 | 2/5/2020 | A | FAIL |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by santiago ramirez - gas line penetration still needs 10mill protective coating installed
|
Rough-in | 2/3/2020 | 2/4/2020 | 2/4/2020 | A | FAIL |
Jack Reynolds
|
|
|
Rough in and gas pressure inspection Phone #: ###-#### Inspection requested via web by santiago ramirez - 20lb gas pressure test fail gauge would not zero - gas line needs protective coating at penetration - fresh air duct needs backdraft damper -
|