Permit Information
Permit NumberMEC20-01221
StatusFinaled
Name ALLEY HEATING & COOLING
Site Address 9667 W LANDMARK ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete HVAC Installation: FURNACE, DUCT-WORK, AC, FIRE-PLACE, BATH VENT, KITCHEN VENT, DRYER VENT, GAS-PIPING, WATER HEATER VENT.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/16/20206/17/20206/17/2020APASS
DetailsBrian Scoles
the correct ac installed, please re-inspect
garage code 0425 or 3484 1225 Phone #: ###-#### Inspection requested via web by Oleg Chervak- final ok
Final6/12/20206/15/20206/15/2020PFAIL
DetailsBrian Scoles
garage code 0425 or 3484 or 1225 Phone #: ###-#### Inspection requested via web by Oleg Chervak- condenser installed does not match approved man j shows carrier has payne installed- replace with right equipment and reschedule
Rough-in4/22/20204/22/20204/22/2020PPASS
DetailsBrian Scoles
WE HAVE NEW APPROVED MANUAL J ON SITE, PLEASE REINSPECT
CORRECTIONS MADE. Phone #: ###-#### Inspection requested via web by Oleg Chervak- R/I on HVAC and fireplace ok
Rough-in4/21/20204/21/20204/21/2020PFAIL
DetailsBrian Scoles
WE UPDATED THE MANUAL J TO REFLECT THE EQUIPMENT ALSO SENT IN FOR RE-REVIEW. CORRECTIONS MADE AS REQUESTED WE WILL HAVE NEW MANUAL J ON SITE FOR YOU. PLEASE CHECK FOR APPROVED ON FINAL. Phone #: ###-#### Inspection requested via web by Oleg Chervak
1- need resubmitted city approved man j onsite for inspection
2- primary condensate needs undo stress above washer box relieved and nuisance drain has a trap in it needs 1/4" per foot grade to outside

notice still posted
Pressure Test4/21/20204/21/20204/21/2020PPASS
DetailsBrian Scoles
WE UPDATED THE MANUAL J TO REFLECT THE EQUIPMENT ALSO SENT IN FOR RE-REVIEW. CORRECTIONS MADE AS REQUESTED WE WILL HAVE NEW MANUAL J ON SITE FOR YOU. PLEASE CHECK FOR APPROVED ON FINAL. Phone #: ###-#### Inspection requested via web by Oleg Chervak- 20lb gas pass
Rough-in4/20/20204/20/20204/20/2020PFAIL
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Oleg Chervak
1- gas gauge doesnt zero out- throw away
2- resubmit man j for approved equipment installed show payne with carrier installed
3- condensate drains both need 1/4" grade to outside per foot and use approved hangers drives not acceptable
4- b vent for w/h in garage will not have 1" clearance after sheetrock will be installed on ceiling and wall- need to firecaulk second floor at floor and attic in chase
5- return needs filter box installed

left notice back window
Pressure Test4/20/20204/20/20204/20/2020PFAIL
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Oleg Chervak- gauge doesnt xero out- throw gauge away