INSP-Sprinkler Rough-in/Hydro | 3/19/2019 | 3/19/2019 | 3/19/2019 | P | PASS |
Troy Cobbley
|
|
|
Above ground hydro test witnessed with no visible pressure loss at the guage.
Call prior to going Phone #: 7753857345 >> Inspection requested via mobile web by Roy Nelsen
|
INSP-Sprinkler Rough-in/Hydro | 3/12/2019 | 3/13/2019 | 3/13/2019 | A | FAIL |
Troy Cobbley
|
|
|
Overhead hydro test failed again due to visible loss on guage.
Call prior to going Phone #: 7753857345 >> Inspection requested via mobile web by Roy Nelsen
|
INSP-Sprinkler Rough-in/Hydro | 3/11/2019 | 3/12/2019 | 3/12/2019 | A | FAIL |
Troy Cobbley
|
|
|
Overhead hydro failed due to visible loss on pressure guage.
Call prior to going Phone #: 7753857345 >> Inspection requested via mobile web by Roy Nelsen
|
INSP-Sprinkler Rough-in/Hydro | 3/8/2019 | 3/11/2019 | 3/11/2019 | A | PASS |
Troy Cobbley
|
|
|
Rough-in passed for the Riser room and piping can be covered. Dry pendant has been relocated in the northwest canopy. Not ready for hydro until water is turned on.
|
INSP-Sprinkler Rough-in | 3/5/2019 | 3/6/2019 | 3/6/2019 | A | CANC |
Troy Cobbley
|
|
|
Call prior to going Phone #: 2083621888 >> Inspection requested via mobile web by Dan
|
INSP-Sprinkler Rough-in | 3/5/2019 | 3/5/2019 | 3/5/2019 | P | PASS |
Troy Cobbley
|
|
|
Rough-in passed. Piping can be covered. One dry pendant is overspaced on the west end of the north side exterior soffit.
As late as possible Phone #: 2083621888 >> Inspection requested via mobile web by Dan Buccino
|
INSP-Sprinkler Rough-in | 3/4/2019 | 3/6/2019 | 3/5/2019 | A | CANC |
Troy Cobbley
|
|
|
As early as possible Phone #: 7753857345 >> Inspection requested via mobile web by Roy Inspection cancelled via mobile web on Tuesday, March 05, 2019.
|
INSP-Sprinkler Rough-in | 2/28/2019 | 3/1/2019 | 3/1/2019 | A | PASS |
Troy Cobbley
|
|
|
Todays inspection was for hanger placement prior to covering by foam insulation. Hangers appear ok. Call prior to going Phone #: 2088719664 >> Inspection requested via mobile web by Jeff
|