Information based on query as of Saturday, April 27, 2024.
Permit Information
Permit NumberPLM18-04192
StatusFinaled
Name PAIGE MECHANICAL GROUP INC
Site Address 711 N CURTIS RD
Project Name 
Customer Number18.7153.22
ePlanReviewNo
Description
New: Med Gas, DWV, Domestic Water, Rain Drains, Fixtures, Med Gas Equipment
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final8/21/20198/22/20198/22/2019APASS
DetailsMatt Wrobel
Phone #: ###-#### Inspection requested via web by Nicholas Paige
Final7/30/20197/30/20197/30/2019PCANC
DetailsMatt Wrobel
remove disposals and pipe drains to floor sinks
talked to plumber about disposals having to be removed per code
Final7/18/20197/19/20197/19/2019PPART
DetailsMatt Wrobel
Phone #: ###-#### Inspection requested via web by Nicholas Paige
final occ pass
Final7/15/20197/17/20197/17/2019APART
DetailsMatt Wrobel
Phone #: ###-#### Inspection requested via web by Nicholas Paige
temp occupancy ok
Other7/8/20197/8/20197/8/2019PDONE
DetailsMatt Wrobel
consultPhone #: ###-#### Inspection requested via web by Nicholas Paige
Final7/3/20197/9/20197/8/2019ACANC
DetailsMatt Wrobel
part final Phone #: ###-#### Inspection requested via web by Nicholas Paige
Final7/3/20197/8/20197/8/2019APART
DetailsMatt Wrobel
part final Phone #: ###-#### Inspection requested via web by Nicholas Paige
temp occ ok A,B, and C.
Med/Gas Systems6/19/20196/20/20196/20/2019APART
DetailsMatt Wrobel
24 hr check pass
Med/Gas Systems6/18/20196/19/20196/19/2019APART
DetailsMatt Wrobel
Phone #: ###-#### Inspection requested via web by Nicholas Paige
start 24 hour test
Other6/4/20196/5/20196/5/2019APART
DetailsMatt Wrobel
consult Phone #: ###-#### Inspection requested via web by Nicholas Paige
walkthru
Other6/4/20196/5/20196/4/2019ACANC
DetailsMatt Wrobel
consult Phone #: ###-#### >> Inspection requested via web by Nicholas Paige Inspection cancelled from web by: Nicholas Paige
Med/Gas Systems5/13/20195/14/20195/14/2019APART
DetailsMatt Wrobel
Phone #: ###-#### Inspection requested via web by Nicholas Paige
med gas test pass
Med/Gas Systems5/9/20195/13/20195/13/2019APART
DetailsMatt Wrobel
Phone #: ###-#### Inspection requested via web by Nicholas Paige
start 24 hr. test
Groundwork5/3/20195/6/20195/6/2019APART
DetailsMatt Wrobel
grease trap piping Phone #: ###-#### Inspection requested via web by Nicholas Paige
Plumbing Rough-in4/12/20194/15/20194/15/2019APART
DetailsMatt Wrobel
Phone #: ###-#### Inspection requested via web by Nicholas Paige
rough in complete except exposed piping in mech room
Med/Gas Systems4/10/20194/11/20194/11/2019APART
DetailsDan Ediger
Phone #: ###-#### Inspection requested via web by Nicholas Paige. start pressure test on service
Plumbing Rough-in4/10/20194/11/20194/11/2019ACANC
DetailsDan Ediger
Grease Duct Rough Phone #: ###-#### Inspection requested via web by Nicholas Paige
under mechanical permit
Plumbing Rough-in4/4/20194/5/20194/5/2019PPART
DetailsMatt Wrobel
Phone #: ###-#### Inspection requested via web by Nicholas Paige
med gAS 24 HR O.K. ROUGH OK
Med/Gas Systems4/3/20194/4/20194/4/2019APART
DetailsDaryl Spivey
Phone #: ###-#### Inspection requested via web by Nicholas Paige
start 24 hour test
Plumbing Rough-in3/28/20193/29/20193/29/2019PPART
DetailsMatt Wrobel
Ryan Phone #: ###-####
sections E,F.G, wall rough in ok to cover
Plumbing Rough-in3/15/20193/15/20193/15/2019PPASS
DetailsMatt Wrobel
e and f raindrains 1st half of e rough in
Med/Gas Systems3/11/20193/12/20193/12/2019APART
DetailsMatt Wrobel
med gas area d ok
Med/Gas Systems3/8/20193/11/20193/11/2019APART
DetailsEric Strole
Phone #: ###-#### Inspection requested via web by Nicholas Paige-Start test 150 psi last 2 rooms area D and stub of mains into area E
Med/Gas Systems3/4/20193/5/20193/5/2019PPART
DetailsMatt Wrobel
med gas test area d pass
Plumbing Rough-in3/1/20193/4/20193/4/2019PPART
DetailsMatt Wrobel
Phone #: ###-#### Inspection requested via web by Nicholas Paige
area d rough in ok to cover
Med/Gas Systems3/1/20193/4/20193/4/2019PPART
DetailsMatt Wrobel
Phone #: ###-#### Inspection requested via web by Nicholas Paige 24 hr test
start
Med/Gas Systems3/1/20193/1/20193/1/2019PCANC
DetailsMatt Wrobel
Phone #: ###-#### >> Inspection requested via web by Nicholas Paige Inspection cancelled from web by: Nicholas Paige
Med/Gas Systems2/25/20192/26/20192/26/2019APART
DetailsMatt Wrobel
med gas pressure test ok
Med/Gas Systems2/21/20192/25/20192/25/2019APART
DetailsMatt Wrobel
Phone #: ###-#### Inspection requested via web by Nicholas Paige
start med gas test mains thru c
Plumbing Rough-in2/19/20192/20/20192/20/2019PPART
DetailsMatt Wrobel
Phone #: ###-#### Inspection requested via web by Nicholas Paige
area c rough in and raindrains ok to cover
Med/Gas Systems2/7/20192/8/20192/8/2019APART
DetailsMatt Wrobel
area b med gas 24 hour test pass
Med/Gas Systems2/6/20192/7/20192/7/2019APART
DetailsMatt Wrobel
Phone #: ###-#### Inspection requested via web by Nicholas Paige
start 24 hour med gas area b
area b interior section rough in ok to cover
Other2/5/20192/5/20192/5/2019PPASS
DetailsMatt Wrobel
inspector conference
Phone #: ###-#### Inspection requested via web by Nicholas Paige
Plumbing Rough-in1/25/20191/28/20191/28/2019PPASS
DetailsMatt Wrobel
Phone #: ###-#### Inspection requested via web by Nicholas Paige
section b exteriors ok to cover center section l;ater this week
Plumbing Rough-in1/18/20191/22/20191/22/2019APASS
DetailsMatt Wrobel
Phone #: ###-#### Inspection requested via web by Nicholas Paige
section a rain drains ok to cover
Plumbing Rough-in1/18/20191/18/20191/18/2019PPASS
DetailsMatt Wrobel
Med/Gas Systems1/16/20191/16/20191/16/2019PPASS
DetailsMatt Wrobel
med gas 24 hour test pass
Med/Gas Systems1/16/20191/16/20191/16/2019PCANC
DetailsMatt Wrobel
Phone #: ###-#### Inspection requested via web by Nicholas Paige
24 hour test pass
Med/Gas Systems1/14/20191/15/20191/15/2019APART
DetailsMatt Wrobel
Phone #: ###-#### Inspection requested via web by Nicholas Paige
10;00 start 24 hour test
Plumbing Rough-in1/14/20191/15/20191/15/2019APART
DetailsMatt Wrobel
Phone #: ###-#### Inspection requested via web by Nicholas Paige
Area "A" waste and vent ok to cover
Groundwork12/17/201812/18/201812/18/2018PPASS
DetailsMatt Wrobel
Phone #: ###-#### Inspection requested via web by Nicholas Paige
Med/Gas Systems12/5/201812/5/201812/5/2018PPART
DetailsMatt Wrobel
start test 130 pm
Med/Gas Systems12/5/201812/5/201812/5/2018PCANC
DetailsMatt Wrobel
Phone #: ###-#### Inspection requested via web by Nicholas Paige
start test 130 pm
Groundwork11/28/201811/29/201811/29/2018PPASS
DetailsMatt Wrobel
Phone #: ###-#### Inspection requested via web by Nicholas Paige
Groundwork11/16/201811/19/201811/19/2018PPASS
DetailsMatt Wrobel
Phone #: ###-#### Inspection requested via web by Nicholas Paige
Groundwork11/7/201811/8/201811/8/2018APASS
DetailsMatt Wrobel
Phone #: ###-#### Inspection requested via web by Nicholas Paige
Groundwork10/22/201810/23/201810/23/2018PPART
DetailsDan Ediger
Phone #: ###-#### Inspection requested via web by Nicholas Paige
areas C and D ok
Groundwork10/18/201810/19/201810/19/2018APART
DetailsDan Ediger
Phone #: ###-#### Inspection requested via web by Nicholas Paige
sewer between east and west corridors.
Groundwork10/18/201810/19/201810/18/2018ACANC
DetailsDan Ediger
Phone #: ###-#### >> Inspection requested via web by Nicholas Paige Inspection cancelled from web by: Nicholas Paige
Groundwork10/9/201810/10/201810/10/2018PPART
DetailsDan Ediger
Phone #: ###-#### Inspection requested via web by Nicholas Paige
Area "B" approved for cover
Groundwork10/4/201810/5/201810/5/2018PPASS
DetailsDan Ediger
section A ok to cover.
Groundwork10/4/201810/5/201810/4/2018PCANC
DetailsDan Ediger
Groundwork10/4/201810/4/201810/4/2018PCANC
DetailsDan Ediger
Phone #: ###-#### Inspection requested via web by Nicholas Paige Rained out