Plumbing Rough-in | 7/7/2020 | 7/8/2020 | 7/8/2020 | A | PASS |
Eric Strole
|
|
|
Phone #: ###-#### Inspection requested via web by Lance Manning
|
Plumbing Rough-in | 7/5/2020 | 7/6/2020 | 7/6/2020 | A | FAIL |
Eric Strole
|
|
|
Phone #: ###-#### Inspection requested via web by Lance Manning-Dwv test fail & vent to close to opening window.
|
Plumbing Rough-in | 6/25/2020 | 6/26/2020 | 6/25/2020 | A | CANC |
Eric Strole
|
|
|
contact is Lance Phone #: ###-#### >> Inspection requested via web by Lance Manning Inspection cancelled from web by: Lance Manning
|
Plumbing Rough-in | 6/25/2020 | 6/25/2020 | 6/25/2020 | P | FAIL |
Dan Ediger
|
|
|
Phone #: ###-#### Inspection requested via web by Lance Manning 1. DWV test failed. 2. Strap DWV at 4ft and end of line/trap arms. 3. Grade all waste at 1/4 ft. 4. Install full size cleanouts w/in 5ft of crawl or above floor.
|