FIR01-00616
| INSP-Sprinkler Rough-in/Hydro | 1/9/2002 | 1/10/2002 | 1/10/2002 12:00:00 AM | A | PART |
|
|
OK to install ceiling tile in areas with sprinkler heads. New areas will need to be inspected when finished. Add upright sprinkler head in east corridor in front of restrooms 1/10/2002 9:11:56 AM
|
FIR01-00592
| INSP-Final Inspection | 1/10/2002 | 1/10/2002 | 1/10/2002 12:00:00 AM | A | FAIL |
|
|
Added by Inspector: 430 On 1/10/2002 9:28:14 AM No approved plans on site. Not all exit doors released when system was in alarm. Tested all fire alarm devices which operated OK. Contractor to provide plans and modify exit sign at warehouse entrance or remove since door is locked.
|
BLD01-01684
| FIRE-Final Inspection | 1/10/2002 | 1/10/2002 | 1/10/2002 12:00:00 AM | P | FAIL |
|
|
provide "door to remain unlocked" sticker on main exit 1/10/2002 2:57:56 PM
|
BLD01-02497
| FIRE-Final Inspection | 1/10/2002 | 1/10/2002 | 1/10/2002 12:00:00 AM | P | NR |
|
|
Added by Inspector: 430 On 1/10/2002 1:31:40 PM Sign off card had no lines for signatures and review notes are missing. Notified contractor that he could pick up a new card with review comments. Inspection to be rescheduled
|
BLD01-02497
| FIRE-Final Inspection | 1/10/2002 | 1/10/2002 | 1/10/2002 12:00:00 AM | P | FAIL |
|
|
Added by Inspector: 430 On 1/10/2002 4:30:28 PM Contractor has correct card and review comments now. Max storage height of 16' is exceeded on racks and some product on racks appears to be encapsulated. Left correction notice with contractor and the Fred Meyer official.
|