Inspections for the day of: Thursday, January 10, 2002.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR01-00616 INSP-Sprinkler Rough-in/Hydro1/9/20021/10/20021/10/2002 12:00:00 AMAPART
OK to install ceiling tile in areas with sprinkler heads. New areas will need to be inspected when finished. Add upright sprinkler head in east corridor in front of restrooms 1/10/2002 9:11:56 AM
FIR01-00592 INSP-Final Inspection1/10/20021/10/20021/10/2002 12:00:00 AMAFAIL
Added by Inspector: 430 On 1/10/2002 9:28:14 AM No approved plans on site. Not all exit doors released when system was in alarm. Tested all fire alarm devices which operated OK. Contractor to provide plans and modify exit sign at warehouse entrance or remove since door is locked.
BLD01-01684 FIRE-Final Inspection1/10/20021/10/20021/10/2002 12:00:00 AMPFAIL
provide "door to remain unlocked" sticker on main exit 1/10/2002 2:57:56 PM
BLD01-02497 FIRE-Final Inspection1/10/20021/10/20021/10/2002 12:00:00 AMPNR
Added by Inspector: 430 On 1/10/2002 1:31:40 PM Sign off card had no lines for signatures and review notes are missing. Notified contractor that he could pick up a new card with review comments. Inspection to be rescheduled
BLD01-02497 FIRE-Final Inspection1/10/20021/10/20021/10/2002 12:00:00 AMPFAIL
Added by Inspector: 430 On 1/10/2002 4:30:28 PM Contractor has correct card and review comments now. Max storage height of 16' is exceeded on racks and some product on racks appears to be encapsulated. Left correction notice with contractor and the Fred Meyer official.