Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR02-00511 INSP-Sprinkler Rough-in/Hydro1/10/20031/10/20031/10/2003 10:25:07 AMPCANC
Rick Can you Look at this to when you are at Lake point today; Phone #: ###-#### Internet Inspection Request from: Mike Timmerman Inspection cancelled from web by: Mike Timmerman
FIR02-00350 FIR-Aging Inspection1/10/20031/10/20031/10/2003 12:00:00 AM PART
left message with Dan B. asking about status 1/10/2003 8:27:08 AM
FIR02-00005 INSP-Sprinkler Rough-in1/10/20031/10/20031/10/2003 12:00:00 AMAFAIL
heads below 22 inches and numerous obstructed in Area A in catwalk area for baggage handling system
BLD02-01716 FIRE-Conference1/9/20031/10/20031/10/2003 12:00:00 AMAPART
Scheduled by a contractor via Hello! on 01/09/2003 at 13:39:54. Contact: ###-####. checked first fire door where it passes through area separation wall; fusible link to deck and at 2nd floor fusible link cuts through sheetrock; will need plate to prevent obstructing release of the cable 1/10/2003 10:12:39 AM
FIR02-00348 INSP-Alarm Testing1/8/20031/10/20031/10/2003 12:00:00 AMPFAIL
Rick at 1:00 PM if Possible
Thanks Mike; Phone #: ###-#### Internet Inspection Request from: Mike Timmerman need shunt trip for elevator shutdown; change maps to reflect combining zone 8 to 6 1/10/2003 3:53:12 PM
FIR02-00511 INSP-Alarm Testing1/10/20031/10/20031/10/2003 12:00:00 AMPPASS
Rick can we look at this at lake point when you are there today

thanks mike; Phone #: ###-#### Internet Inspection Request from: Mike Timmerman