Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD02-02581 FIRE-Final Inspection1/9/20031/10/20031/10/2003 12:00:00 AMAFAIL
replace the missing sprinkler canopies and adjust the sprinkler pendants that are hanging below the ceiling 1/10/2003 11:26:05 AM
MIS03-00006 FIR-Final1/10/20031/10/20031/10/2003 12:00:00 AMPFAIL
provide fire extinguishers with current inspection tags and mounted at 48" AFF in both of the buildings, repair exit signs in the showroom building, provide exits signs per the structural inspectors review note #4, remove or disable the second lock on the lower door in the showroom building 1/10/2003 3:27:05 PM
FIR02-00268 INSP-Final Inspection1/9/20031/10/20031/10/2003 12:00:00 AMPFAIL
relocate smoke detector to more than 3' from the supply register and test, the smoke detector that was installed is not the smoke detector that was submitted. Provide approved smoke detector or resubmit new smoke detector information including compatibility listig to Sam Rogers for approval. This may require revised battery calcs. Duct detector in office area des not shut down HVAC unit when ativated, relocate duct detector in shop area out of the 90 degree bend and test, pressure switch on the sprinkler riser did not send signal to the FACP , test tamper switch, install electric alarm bell, provide a map per review note #4, rovide signs on the FACP door and the fire sprinkler riser door per note #12 1/10/2003 3:36:22 PM