ELE05-02848
| ELE-Aging Inspection | 1/10/2006 | 1/10/2006 | 1/10/2006 2:19:27 PM | | PART |
|
|
wsuc
|
ELE05-04026
| Electrical Rough-In | 1/10/2006 | 1/10/2006 | 1/10/2006 2:13:35 PM | P | PART |
|
|
ceiling; Phone #: ###-#### Internet Inspection Request from: Jim Williams ceilings ok
|
ELE05-01869
| Final | 1/10/2006 | 1/10/2006 | 1/10/2006 2:13:01 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Jim Williams ok no card
|
ELE06-00095
| Electrical Rough-In | 1/10/2006 | 1/10/2006 | 1/10/2006 1:31:15 PM | P | FAIL |
|
|
zane ###-#### cor. do not cover called, BCC no violations retained needs clearence for p/s use manufactures breakers, #12 & #14 mixed watch for overcurrent prtion 3 way stairs basement, 300.4 nail plates 11/4"" 314.16 box fill 110.3 replace all damaged boxes ( holes drilled in the side, broken factory clamps, 314.43 no screws in plastic boxes, COW
|
ELE05-04497
| Electrical Rough-In | 1/10/2006 | 1/10/2006 | 1/10/2006 12:34:01 PM | P | PASS |
|
|
trench inspection please///cathy; Phone #: ###-#### Internet Inspection Request from: Barbara Moore all u/g ok
|
ELE05-04255
| Final | 1/10/2006 | 1/10/2006 | 1/10/2006 12:00:50 PM | P | PASS |
|
|
tom; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok card signed
|
ELE05-03235
| Final | 1/9/2006 | 1/10/2006 | 1/10/2006 10:55:52 AM | A | PASS |
|
|
rick; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok survey posted called needs outlet wall under stairs
|
ELE06-00086
| Temporary Service | 1/9/2006 | 1/10/2006 | 1/10/2006 10:32:29 AM | A | PASS |
|
|
Brannon; Phone #: ###-#### Internet Inspection Request from: Rowdy Monroe t/s u/g new ok
|
ELE05-03254
| Final | 1/9/2006 | 1/10/2006 | 1/10/2006 10:15:47 AM | A | FAIL |
|
|
david; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie--call 1st before insp cor. met owner 314.20 outside boxes shall be flush with siding,, 314.17 connectors for cables, 250.148 grd boxes, 110.14 all splices and terminals made up tight, pull all recepts from boxes so I can insoect and install outside fixtures
|
ELE06-00069
| Rough-In Permanent Service | 1/9/2006 | 1/10/2006 | 1/10/2006 9:22:02 AM | A | FAIL |
|
|
neal; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie cor. do not cover both units called, 300.4 nail plates and 11/4", 314.16 box fill , 334.23 protect romex attic accesses, 210.52 outlets for wall space liv rm by pantry pomona unit kit wall by pantry reawy init, 110.12 replace plastic boxes with extra KOs broken out, only one p/s this is a duplex both p/s inspected, protect panels
|
ELE05-04525
| Electrical Rough-In | 1/9/2006 | 1/10/2006 | 1/10/2006 8:28:02 AM | A | PASS |
|
|
KEN nOTE: PLEASE CALL 1/2 HR IF PR0BLEM; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie r/i ok
|