Inspections for the day of: Wednesday, January 10, 2007.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-04235 Final1/10/20071/10/20071/10/2007 4:05:21 PMPPASS
ok to final
ELE07-00076 Rough-In Permanent Service1/10/20071/10/20071/10/2007 4:04:06 PMPFAIL
brandon; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called, left corr notice, nec 300.4(A)&(B) edge of holes and nm cable shall be 1 1/4" from edge of framing member,314.17(C) nm cable shall be stapled within 8" of box, 210.52(A) recpt shall be placed in entry, 410.8 closet light shall be 12" from shelf, 210.52(E) recpt shall be installed at back,210.63 recpt shall be within 25' of a/c, BCC all make-up shall be done(kitchen), shall see u/g to garage
ELE06-00109 Electrical Rough-In1/9/20071/10/20071/10/2007 3:58:49 PMAFAIL
william ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called gave corr notice, nec 312.5 all conductors entering enclosure shall have abrasion protection,200.6(B) grounded conductor shall be identified, nm cable shall not be stapled on edge, BCC all make-up shall be done, shall see u/g before cover, all boxes shall be installed
ELE06-04641 Final1/10/20071/10/20071/10/2007 3:22:20 PMPPASS
Please call Paul @###-#### before going so access can be insured. thanks Paul Phone #: ###-#### ok to final
ELE06-03597 Rough-In Permanent Service1/10/20071/10/20071/10/2007 3:04:00 PMPFAIL
Scheduled by a contractor via Hello! on 1/10/2007 at 10:21:02 AM. Contact: ###-####. called, told contr that corrections weren't ready, wrote corr notice, nec 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing members or shall use steel plates, BCC address shall be posted, talked with bldr, they are requesting change of adress, told each location needs address
ELE06-02762 Electrical Rough-In1/10/20071/10/20071/10/2007 2:19:11 PMPPART
jim; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ric garage only ok, looked at sws, recpts and lighting. Will look at rest of subpanel once fed.
ELE07-00098 Rough-In Permanent Service1/10/20071/10/20071/10/2007 1:51:35 PMPPASS
Lynn; Phone #: ###-#### this is for two units Internet Inspection Request from: Cathy Weisshaupt ric ok, p/s u/g n ok
ELE06-02121 Electrical Rough-In1/10/20071/10/20071/10/2007 1:22:50 PMPFAIL
lauren; Phone #: ###-#### Internet Inspection Request from: Victoria Beall called, left message, tried to explain 1 1/4" left and initialed card and corr notice
ELE06-04355 Permanent Service1/9/20071/10/20071/10/2007 9:46:10 AMAPASS
Phone #: ###-#### p/s, exst meter, n, ok
ELE06-04697 Electrical Rough-In1/9/20071/10/20071/10/2007 9:13:08 AMAPASS
randy; Phone #: ###-#### Internet Inspection Request from: Victoria Beall walls only ok to cover
ELE07-00010 Permanent Service1/9/20071/10/20071/10/2007 8:46:09 AMPCANC
Scheduled by a contractor via Hello! on 1/9/2007 at 8:31:16 PM. Contact: ###-####. Inspection cancelled from web by: Victoria Beall
ELE06-03529 Final1/9/20071/10/20071/10/2007 8:18:27 AMAPASS
jeff ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to final, signed occ card