ELE06-04235
| Final | 1/10/2007 | 1/10/2007 | 1/10/2007 4:05:21 PM | P | PASS |
|
|
ok to final
|
ELE07-00076
| Rough-In Permanent Service | 1/10/2007 | 1/10/2007 | 1/10/2007 4:04:06 PM | P | FAIL |
|
|
brandon; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called, left corr notice, nec 300.4(A)&(B) edge of holes and nm cable shall be 1 1/4" from edge of framing member,314.17(C) nm cable shall be stapled within 8" of box, 210.52(A) recpt shall be placed in entry, 410.8 closet light shall be 12" from shelf, 210.52(E) recpt shall be installed at back,210.63 recpt shall be within 25' of a/c, BCC all make-up shall be done(kitchen), shall see u/g to garage
|
ELE06-00109
| Electrical Rough-In | 1/9/2007 | 1/10/2007 | 1/10/2007 3:58:49 PM | A | FAIL |
|
|
william ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called gave corr notice, nec 312.5 all conductors entering enclosure shall have abrasion protection,200.6(B) grounded conductor shall be identified, nm cable shall not be stapled on edge, BCC all make-up shall be done, shall see u/g before cover, all boxes shall be installed
|
ELE06-04641
| Final | 1/10/2007 | 1/10/2007 | 1/10/2007 3:22:20 PM | P | PASS |
|
|
Please call Paul @###-#### before going so access can be insured. thanks Paul Phone #: ###-#### ok to final
|
ELE06-03597
| Rough-In Permanent Service | 1/10/2007 | 1/10/2007 | 1/10/2007 3:04:00 PM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 1/10/2007 at 10:21:02 AM. Contact: ###-####. called, told contr that corrections weren't ready, wrote corr notice, nec 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing members or shall use steel plates, BCC address shall be posted, talked with bldr, they are requesting change of adress, told each location needs address
|
ELE06-02762
| Electrical Rough-In | 1/10/2007 | 1/10/2007 | 1/10/2007 2:19:11 PM | P | PART |
|
|
jim; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ric garage only ok, looked at sws, recpts and lighting. Will look at rest of subpanel once fed.
|
ELE07-00098
| Rough-In Permanent Service | 1/10/2007 | 1/10/2007 | 1/10/2007 1:51:35 PM | P | PASS |
|
|
Lynn; Phone #: ###-#### this is for two units Internet Inspection Request from: Cathy Weisshaupt ric ok, p/s u/g n ok
|
ELE06-02121
| Electrical Rough-In | 1/10/2007 | 1/10/2007 | 1/10/2007 1:22:50 PM | P | FAIL |
|
|
lauren; Phone #: ###-#### Internet Inspection Request from: Victoria Beall called, left message, tried to explain 1 1/4" left and initialed card and corr notice
|
ELE06-04355
| Permanent Service | 1/9/2007 | 1/10/2007 | 1/10/2007 9:46:10 AM | A | PASS |
|
|
Phone #: ###-#### p/s, exst meter, n, ok
|
ELE06-04697
| Electrical Rough-In | 1/9/2007 | 1/10/2007 | 1/10/2007 9:13:08 AM | A | PASS |
|
|
randy; Phone #: ###-#### Internet Inspection Request from: Victoria Beall walls only ok to cover
|
ELE07-00010
| Permanent Service | 1/9/2007 | 1/10/2007 | 1/10/2007 8:46:09 AM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 1/9/2007 at 8:31:16 PM. Contact: ###-####. Inspection cancelled from web by: Victoria Beall
|
ELE06-03529
| Final | 1/9/2007 | 1/10/2007 | 1/10/2007 8:18:27 AM | A | PASS |
|
|
jeff ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to final, signed occ card
|