Inspections for the day of: Thursday, January 10, 2008.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-01468 Final1/10/20081/10/20081/10/2008 4:14:20 PMPPASS
kelly Phone #: ###-#### ok to final, corrections made
ELE07-03564 Permanent Service1/9/20081/10/20081/10/2008 2:32:59 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Jim Williams p/s, o/h, rec ok, for 5 meters
ELE08-00072 Rough-In Permanent Service1/9/20081/10/20081/10/2008 1:35:55 PMPPASS
dave Phone #: ###-#### u/g only house to shed ok to cover, p/s u/g rec ok
ELE07-03967 Electrical Rough-In1/10/20081/10/20081/10/2008 1:05:23 PMPCANC
This is for a panel inspection, contact on this job is Toby Groves ###-#### Phone #: ###-#### Internet Inspection Request from: Debby Ellis see conference
ELE07-03967 Conference1/10/20081/10/20081/10/2008 1:05:11 PMPDONE
This is for a panel inspection, contact on this job is Toby Groves ###-#### Phone #: ###-#### Internet Inspection Request from: Debby Ellis looked at ducts over switchgear, talked with 412 and 324 and since there is no service change, ducts over gear ok as installed
ELE07-03533 Final1/9/20081/10/20081/10/2008 12:18:09 PMAFAIL
Scheduled by a contractor via Hello! on 1/9/2008 at 12:05:16 PM. Contact: ###-####. called, left corr notice, nec 408.4 circuit directory shall be clear, concise, complete, and explanatory-subpanel, 314.25 completed installations shall have covers for each box- bottom of stairs ceiling
ELE08-00034 Permanent Service1/9/20081/10/20081/10/2008 10:01:20 AMAPASS
jake Phone #: ###-#### p/s, exst meter pak, rec, ok
ELE07-04079 Final1/9/20081/10/20081/10/2008 9:48:33 AMAFAIL
Scheduled by a contractor via Hello! on 1/9/2008 at 12:03:54 PM. Contact: ###-####. called electrician, left correction notice, nec 406.4 receptacles in kitchen and dining area shall be securely mounted, 410.4 fixture in downstairs shower shall be listed for wet location, 410.8(B) closet fixture shall be completely enclosed
ELE08-00013 Electrical Rough-In1/9/20081/10/20081/10/2008 8:31:55 AMAPASS
John Fivecoat is the electrician @###-####, please provide rough in inspection Phone #: ###-#### Internet Inspection Request from: gary batten ric ok basement area only