Inspections for the day of: Monday, January 10, 2011.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00263 FIR-Aging Inspection1/10/20111/10/20111/12/2011 1:58:40 PM DEFR
I spoke to Matt again about getting the permit voided since the building has been demolished.
BLD10-02170 FIRE-Conference1/10/20111/10/20111/10/2011 3:14:49 PMPDONE
Carl Westfall is ok with the exit sign that was shown to be installed at the top of the stairs to the mezzanine to be deleted.
FIR10-00548 INSP-Final Inspection1/7/20111/10/20111/10/2011 3:10:28 PMAFAIL
Todays test included testing of the flow switch, PIV and EOL voltage for the audio/visual devices in the new tenant space. Supervision of the new NAC panel by the new FACP was verified as well. Still need the duct smoke detector locations addressed/tested, correct descriptions at teh new remote annunciator and the correct documentation as per telephone conversations with the plan reviewer.
BLD10-01509 FIRE-Final Inspection1/7/20111/10/20111/10/2011 11:01:26 AMAPASS
Life safety passed.
FIR10-00498 INSP-Final Inspection1/7/20111/10/20111/10/2011 11:00:12 AMAPASS
Permit finaled