FIR09-00263
| FIR-Aging Inspection | 1/10/2011 | 1/10/2011 | 1/12/2011 1:58:40 PM | | DEFR |
|
|
I spoke to Matt again about getting the permit voided since the building has been demolished.
|
BLD10-02170
| FIRE-Conference | 1/10/2011 | 1/10/2011 | 1/10/2011 3:14:49 PM | P | DONE |
|
|
Carl Westfall is ok with the exit sign that was shown to be installed at the top of the stairs to the mezzanine to be deleted.
|
FIR10-00548
| INSP-Final Inspection | 1/7/2011 | 1/10/2011 | 1/10/2011 3:10:28 PM | A | FAIL |
|
|
Todays test included testing of the flow switch, PIV and EOL voltage for the audio/visual devices in the new tenant space. Supervision of the new NAC panel by the new FACP was verified as well. Still need the duct smoke detector locations addressed/tested, correct descriptions at teh new remote annunciator and the correct documentation as per telephone conversations with the plan reviewer.
|
BLD10-01509
| FIRE-Final Inspection | 1/7/2011 | 1/10/2011 | 1/10/2011 11:01:26 AM | A | PASS |
|
|
Life safety passed.
|
FIR10-00498
| INSP-Final Inspection | 1/7/2011 | 1/10/2011 | 1/10/2011 11:00:12 AM | A | PASS |
|
|
Permit finaled
|