Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00263 FIR-Aging Inspection1/10/20121/10/20121/11/2012 11:20:51 AM DONE
FIR09-00680 FIR-Aging Inspection1/10/20121/10/20121/11/2012 11:16:24 AM NR
This project has been turned over to the fire marshal for enforcement.
FIR09-00228 FIR-Aging Inspection1/10/20121/10/20121/11/2012 10:12:51 AM NR
I spoke to Bill again about getting a final on this permit.
FIR11-00543 INSP-Sprinkler Rough-in1/10/20121/10/20121/10/2012 3:45:58 PMPPASS
A revised set of as-builts were issued today with the date of 1-10-1012. These are now the set of drawings that I'm inspecting to. Anyway area "B" is now approved for cover. I went over possible future issues with Scott about wall heights at the west end of the building and that if the walls are not full height as had been stated to Tim Frost that additional hydraulic calculation areas may be need due to open spaces above the ceilings.
FIR11-00381 INSP-Final Inspection1/9/20121/10/20121/10/2012 11:03:41 AMAFAIL
Provide for location and testing of EOL voltage drops. The new manual pull station located in the waiting room is located too far from the door and placed too low. See IFC 907.5.2. The duct smoke detectors tested ok.
BLD11-02804 FIRE-Final Inspection1/9/20121/10/20121/10/2012 10:59:52 AMAFAIL
Provide single action hardware on one of the main storefront exit doors. The other door can remain keyed except that it will need the sticker. Also provide provide single action hardware on both doors that exit out through the office or remove the exit sign and only provide single action hardware on the exterior office exit door.