Inspections for the day of: Thursday, January 10, 2019.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR18-00464 INSP-Sprinkler Rough-in/Hydro1/9/20191/10/20191/10/2019 3:38:31 PMPDONE
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed.

Phone #: ###-#### Inspection requested via web by Matthew Lewis
FIR18-00826 INSP-Sprinkler Rough-in/Hydro1/10/20191/10/20191/10/2019 3:37:13 PMPDONE
Hydrostatic test for overhead fire sprinkler piping witnessed with anti-freeze, no pressure loss observed at riser gauges.

Gerarrdo is the contact. Phone #: ###-#### Inspection requested via web by Stan Beus
FIR18-00808 INSP-Final Inspection1/8/20191/10/20191/10/2019 2:26:50 PMPFAIL
Resubmit plans showing new NAC panel. Need to meet sound requirements in discussed areas. Provide calculations for 3rd circuit used.

This inspection is being requested to be done after 1:30pm as they are having to coordinate with the Boise Center on the Grove. Crane Alarm''s technician for this final is Eric Nelson ###-#### Phone #: ###-#### Inspection requested via web by Cheyenne Zumstein
BLD18-04081 FIRE-Final Inspection1/9/20191/10/20191/10/2019 10:14:18 AMAPASS
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers are placed in common areas with current inspection tags. Final life fire safety inspection for area of work complete.

Eric Phone #: ###-####
FIR18-00942 INSP-Sprinkler Rough-in1/8/20191/10/20191/10/2019 9:19:05 AMAPASS
Tenting inspection complete, all tenting in place at time of inspection, all fire sprinkler piping approved for cover.

Tenting inspection Phone #: ###-#### Inspection requested via web by Anthony Minichiello
BLD18-02667 FIRE-Final Inspection1/10/20191/10/20191/10/2019 8:56:04 AMAPASS
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguisher will be placed in discussed location. Final life fire safety inspection for area of work complete.

FIR18-00687 INSP-Final Inspection1/10/20191/10/20191/10/2019 8:53:37 AMAPASS
Final fire alarm inspection for area of work complete.

Phone #: ###-#### Inspection requested via web by Gary Gambino