FIR18-00464
| INSP-Sprinkler Rough-in/Hydro | 1/9/2019 | 1/10/2019 | 1/10/2019 3:38:31 PM | P | DONE |
|
|
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed.
Phone #: ###-#### Inspection requested via web by Matthew Lewis
|
FIR18-00826
| INSP-Sprinkler Rough-in/Hydro | 1/10/2019 | 1/10/2019 | 1/10/2019 3:37:13 PM | P | DONE |
|
|
Hydrostatic test for overhead fire sprinkler piping witnessed with anti-freeze, no pressure loss observed at riser gauges.
Gerarrdo is the contact. Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00808
| INSP-Final Inspection | 1/8/2019 | 1/10/2019 | 1/10/2019 2:26:50 PM | P | FAIL |
|
|
Resubmit plans showing new NAC panel. Need to meet sound requirements in discussed areas. Provide calculations for 3rd circuit used.
This inspection is being requested to be done after 1:30pm as they are having to coordinate with the Boise Center on the Grove. Crane Alarm''s technician for this final is Eric Nelson ###-#### Phone #: ###-#### Inspection requested via web by Cheyenne Zumstein
|
BLD18-04081
| FIRE-Final Inspection | 1/9/2019 | 1/10/2019 | 1/10/2019 10:14:18 AM | A | PASS |
|
|
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers are placed in common areas with current inspection tags. Final life fire safety inspection for area of work complete.
Eric Phone #: ###-####
|
FIR18-00942
| INSP-Sprinkler Rough-in | 1/8/2019 | 1/10/2019 | 1/10/2019 9:19:05 AM | A | PASS |
|
|
Tenting inspection complete, all tenting in place at time of inspection, all fire sprinkler piping approved for cover.
Tenting inspection Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
BLD18-02667
| FIRE-Final Inspection | 1/10/2019 | 1/10/2019 | 1/10/2019 8:56:04 AM | A | PASS |
|
|
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguisher will be placed in discussed location. Final life fire safety inspection for area of work complete.
|
FIR18-00687
| INSP-Final Inspection | 1/10/2019 | 1/10/2019 | 1/10/2019 8:53:37 AM | A | PASS |
|
|
Final fire alarm inspection for area of work complete.
Phone #: ###-#### Inspection requested via web by Gary Gambino
|