ELE04-03682 Rough-In Permanent Service1/10/20051/11/20051/11/2005 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 1/10/2005 at 11:53:46 AM. Contact: ###-####. r/i upstairs and down office areas
p/s u/g new ok 1/11/2005 8:27:55 AM
ELE05-00091 Temporary Service1/10/20051/11/20051/11/2005 12:00:00 AMAFAIL
please call richard ###-#### for information
cor. called 110.3(B) manufacture states use 2 pole breakers only 1/11/2005 9:05:29 AM
ELE04-04135 Electrical Rough-In1/10/20051/11/20051/11/2005 12:00:00 AMAFAIL
Bedroom and bathroom ready for inspection.; Phone #: ###-#### Internet Inspection Request from: Joe Thomas cor. dont cover , fee due posted called box fill, correct violations in old 3 gang box bath rm provide lighting back door bed rm 1/11/2005 10:08:57 AM
ELE04-00825 Permanent Service1/10/20051/11/20051/11/2005 12:00:00 AMAPASS
Need inspection for second subfed panel in spa for power company connection.; Phone #: ###-#### Internet Inspection Request from: Monty Adkinson p/s u/g for meter ok 1/11/2005 10:27:18 AM
ELE05-00033 Rough-In Permanent Service1/11/20051/11/20051/11/2005 12:00:00 AMPPASS
lloyd; Phone #: ###-#### Internet Inspection Request from: Barbara Moore r/i ok up and down p/s o/h rec ok 1/11/2005 1:28:49 PM
ELE05-00028 Electrical Rough-In1/10/20051/11/20051/11/2005 12:00:00 AMPFAIL
please call half hour prior to inspection so he can let ya in///jack; Phone #: ###-#### Internet Inspection Request from: Barbara Moore cor. posted met contractor 300.4(A)(1)&(D), 210.52(C)(1) countertop outlet spacing, 210.52(D)&210.11(C)(3) outlet within 3ft of sink,and 20 amp bath circuit, 250.140 shall use SE type cable from P/S or 10/3 romex for cook top 1/11/2005 2:09:46 PM
ELE04-03650 Rough-In Permanent Service1/10/20051/11/20051/11/2005 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 1/10/2005 at 9:21:20 AM. Contact: ###-####. r/i ok all 4 units
p/s u/g new ok 1/11/2005 3:36:51 PM
ELE04-03654 Rough-In Permanent Service1/10/20051/11/20051/11/2005 12:00:00 AMPPASS
VIVIAN ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie r/i ok all 4 units