Inspections for the day of: Tuesday, January 11, 2005.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-00077 Temporary Service1/10/20051/11/20051/11/2005 12:00:00 AMAPASS
Internet Inspection Request from: Bob Glenn 1/11/2005 8:57:57 AM t/s u/g n ok 1/11/2005 8:58:30 AM
ELE04-04094 Final1/10/20051/11/20051/11/2005 12:00:00 AMAPASS
contact Miles. Thank You.; Phone #: ###-#### Internet Inspection Request from: Wendy Waters ok to final 1/11/2005 9:55:32 AM
ELE04-03595 Permanent Service1/10/20051/11/20051/11/2005 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 1/10/2005 at 3:33:50 PM. Contact: ###-####. 250.56 a single electrode shall be augmented by one additional electrode if 25 ohms or less. called contr. 1/11/2005 9:32:26 AM
ELE04-04059 Final1/11/20051/11/20051/11/2005 12:00:00 AMANR
Phone #: ###-#### Internet Inspection Request from: Richard Jones need power on to final. see comment for p/s. 1/11/2005 8:40:12 AM
ELE04-04059 Permanent Service1/11/20051/11/20051/11/2005 12:00:00 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Richard Jones left correction notice: 408.4 All circuits shall be identified, 200.7(A)(1) White wire shall be used for grounded circuit conductor only, 250.53(B) Electrodes shall be minimum 6' apart. Will allow power to come in,he will fix today. Can't do final till power on.Need to check inside panel and well at final. p/s o/h n ok. 1/11/2005 8:38:56 AM
ELE05-00098 Final1/11/20051/11/20051/11/2005 12:00:00 AMPPASS
Dan; Phone #: ###-#### Internet Inspection Request from: Jan Rice elect finishing ground rod. corrections made, will add couple of bushings in subpanel. Was existing o/h, but blew down in wind storm. ok to final. p/s o/h n ok 1/11/2005 12:24:37 PM
ELE04-03823 Final1/11/20051/11/20051/11/2005 12:00:00 AMPPASS
darrell; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok to final 1/11/2005 4:28:54 PM
ELE04-03824 Final1/11/20051/11/20051/11/2005 12:00:00 AMPPASS
darrell; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie called contractor and told him about 1 recpt that was pulled out of wall. ok to final 1/11/2005 1:58:48 PM