FIR04-00383
| INSP-Alarm Testing | 1/10/2005 | 1/11/2005 | 1/11/2005 12:00:00 AM | A | FAIL |
|
|
Resubmit plans showing the additional duct smoke detector and change the text at the remote annunciator to show "kitchen hood" 1/11/2005 1:58:13 PM
|
FIR04-00403
| INSP-Final Inspection | 1/10/2005 | 1/11/2005 | 1/11/2005 12:00:00 AM | A | PASS |
|
|
Suppression system operated correctly 1/11/2005 1:32:27 PM
|
FIR04-00780
| INSP-Final Inspection | 1/10/2005 | 1/11/2005 | 1/11/2005 12:00:00 AM | A | FAIL |
|
|
Need ceiling tile in around pendants and missing canopies. Need annual inspection for the sprinkler system. Sprinkler piping is ok to cover. 1/11/2005 10:18:15 AM
|
FIR04-00605
| INSP-Final Inspection | 1/10/2005 | 1/11/2005 | 1/11/2005 12:00:00 AM | A | FAIL |
|
|
The zone labels for the tampers and riser rooms for learning center need changed to be more specific as to device and location. Tamper switches come in as troubles on this system too. The system in the theatres was not tested. Inspection for the new system was started at the duct detectors in DBSI's space. At the first detector inspected I found that the detector was not mounted in the air stream and upon closer inspection found that the detector was barely mounted to the duct and basicaly came off the ductwork into my hand. The sample tube was installed backwards and upside down and the foam donut seals were lying unistalled in a bag on the ceiling. Inspection was stopped. Resubmittals are also required due to additional anti-freeze tamper switches existing but not shown on the plans. 1/11/2005 2:08:57 PM
|
FIR04-00699
| INSP-Final Inspection | 1/10/2005 | 1/11/2005 | 1/11/2005 12:00:00 AM | A | PASS |
|
|
Fire alarm finaled 1/11/2005 10:19:16 AM
|
BLD04-01727
| FIRE-Conference | 1/11/2005 | 1/11/2005 | 1/11/2005 12:00:00 AM | P | DONE |
|
|
Went over live safety notes with contrator 1/11/2005 5:00:18 PM
|