Inspections for the day of: Wednesday, January 11, 2006.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-02067 ELE-Aging Inspection1/11/20061/11/20061/11/2006 4:15:42 PM DONE
see final
ELE05-03904 Final1/11/20061/11/20061/11/2006 4:06:24 PMPPASS
cody ###-#### for access called contr, left message, left survey,406.4 front recpt shall be rigidly held in place, ok to final
ELE04-01682 ELE-Aging Inspection1/11/20061/11/20061/11/2006 3:08:12 PM DONE
see final
ELE05-02212 ELE-Aging Inspection1/11/20061/11/20061/11/2006 2:22:24 PM DONE
see final
ELE06-00103 Temporary Service1/11/20061/11/20061/11/2006 2:19:46 PMPFAIL
brian -###-#### called contr, left corr notice, 250.53(G) rod electrode shall be such that upper end is flush with or below gnd, 250.24(A)(1) gndg electrode conductor shall be connected to gnded conductor bus,110.14(A) connections shall be tight,110.3(B) equipment shall be installed per instructions,all screws provided, 250.52(A)(5)(b) steel electrode shall be at least 5/8" diameter, fee due
ELE06-00076 Final1/11/20061/11/20061/11/2006 11:55:49 AMPCANC
REINSPECTIONAL ON TEMP SERVICE READY; Phone #: ###-#### Internet Inspection Request from: JENNY EMEL see t/s
ELE06-00076 Final1/10/20061/11/20061/11/2006 9:42:09 AMAFAIL
TEMPARY SERVICE, READY FOR IPCO WED. AM; Phone #: ###-#### Internet Inspection Request from: JENNY EMEL called contr, left message, left corr noyice, 312.5 abrasion protection shall be provided for conductors entering enclosures, 408.4 circuit directory shall be provided, 314.15(A) fittings installed in wet locations shall be listed for use in wet locations, BCC job id sticker shall be posted, 31423(A) box shall be rigidly mounted
ELE05-03904 Final1/10/20061/11/20061/11/2006 8:38:47 AMACANC
call for garage code///cody; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa called contr for access, code won't work, said they will have to recall.
ELE05-00855 Permanent Service1/10/20061/11/20061/11/2006 8:13:28 AMACANC
contact: Lyle Dean; Phone #: ###-#### Internet Inspection Request from: Deb McCoy wrong permit , they will fix and recall
ELE05-02067 Final1/11/20061/11/20061/11/2006 12:00:00 AMAPASS
looked at signs, ok to final
ELE06-00076 Temporary Service1/11/20061/11/20061/11/2006 12:00:00 AMPPASS
REINSPECTIONAL ON TEMP SERVICE READY; Phone #: ###-#### Internet Inspection Request from: JENNY EMEL corrections made, t/s o/h n ok
ELE05-02212 Final1/11/20061/11/20061/11/2006 12:00:00 AMPPASS
looked at signs, ok to final
ELE04-01682 Final1/11/20061/11/20061/11/2006 12:00:00 AMPPASS
called contr to install press sw cover, ok to final
ELE05-03916 Final1/11/20061/11/20061/11/2006 12:00:00 AMPFAIL
called contr, left corr notice, contr had us look at data for cable, but the ampacity did not agree with NEC. Also data appeared to be generic for several types x-ray machines. Told contr he should disconnect power until evaluation was done. BCC 4-05-33(A) Equipment shall be listed as an assembly,450.13(B) transformer shall be readily accessible,400.5(A) st cord ampacity shall be per disconnect,400.8(1) cord shall not be used for fixed wiring,517.78shall apply for grounding ,517.13 shall apply for redundant gndg,250.118 shall apply for equipment gndg,110.2 equipment shall be acceptable only if approved