ELE05-02067
| ELE-Aging Inspection | 1/11/2006 | 1/11/2006 | 1/11/2006 4:15:42 PM | | DONE |
|
|
see final
|
ELE05-03904
| Final | 1/11/2006 | 1/11/2006 | 1/11/2006 4:06:24 PM | P | PASS |
|
|
cody ###-#### for access called contr, left message, left survey,406.4 front recpt shall be rigidly held in place, ok to final
|
ELE04-01682
| ELE-Aging Inspection | 1/11/2006 | 1/11/2006 | 1/11/2006 3:08:12 PM | | DONE |
|
|
see final
|
ELE05-02212
| ELE-Aging Inspection | 1/11/2006 | 1/11/2006 | 1/11/2006 2:22:24 PM | | DONE |
|
|
see final
|
ELE06-00103
| Temporary Service | 1/11/2006 | 1/11/2006 | 1/11/2006 2:19:46 PM | P | FAIL |
|
|
brian -###-#### called contr, left corr notice, 250.53(G) rod electrode shall be such that upper end is flush with or below gnd, 250.24(A)(1) gndg electrode conductor shall be connected to gnded conductor bus,110.14(A) connections shall be tight,110.3(B) equipment shall be installed per instructions,all screws provided, 250.52(A)(5)(b) steel electrode shall be at least 5/8" diameter, fee due
|
ELE06-00076
| Final | 1/11/2006 | 1/11/2006 | 1/11/2006 11:55:49 AM | P | CANC |
|
|
REINSPECTIONAL ON TEMP SERVICE READY; Phone #: ###-#### Internet Inspection Request from: JENNY EMEL see t/s
|
ELE06-00076
| Final | 1/10/2006 | 1/11/2006 | 1/11/2006 9:42:09 AM | A | FAIL |
|
|
TEMPARY SERVICE, READY FOR IPCO WED. AM; Phone #: ###-#### Internet Inspection Request from: JENNY EMEL called contr, left message, left corr noyice, 312.5 abrasion protection shall be provided for conductors entering enclosures, 408.4 circuit directory shall be provided, 314.15(A) fittings installed in wet locations shall be listed for use in wet locations, BCC job id sticker shall be posted, 31423(A) box shall be rigidly mounted
|
ELE05-03904
| Final | 1/10/2006 | 1/11/2006 | 1/11/2006 8:38:47 AM | A | CANC |
|
|
call for garage code///cody; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa called contr for access, code won't work, said they will have to recall.
|
ELE05-00855
| Permanent Service | 1/10/2006 | 1/11/2006 | 1/11/2006 8:13:28 AM | A | CANC |
|
|
contact: Lyle Dean; Phone #: ###-#### Internet Inspection Request from: Deb McCoy wrong permit , they will fix and recall
|
ELE05-02067
| Final | 1/11/2006 | 1/11/2006 | 1/11/2006 12:00:00 AM | A | PASS |
|
|
looked at signs, ok to final
|
ELE06-00076
| Temporary Service | 1/11/2006 | 1/11/2006 | 1/11/2006 12:00:00 AM | P | PASS |
|
|
REINSPECTIONAL ON TEMP SERVICE READY; Phone #: ###-#### Internet Inspection Request from: JENNY EMEL corrections made, t/s o/h n ok
|
ELE05-02212
| Final | 1/11/2006 | 1/11/2006 | 1/11/2006 12:00:00 AM | P | PASS |
|
|
looked at signs, ok to final
|
ELE04-01682
| Final | 1/11/2006 | 1/11/2006 | 1/11/2006 12:00:00 AM | P | PASS |
|
|
called contr to install press sw cover, ok to final
|
ELE05-03916
| Final | 1/11/2006 | 1/11/2006 | 1/11/2006 12:00:00 AM | P | FAIL |
|
|
called contr, left corr notice, contr had us look at data for cable, but the ampacity did not agree with NEC. Also data appeared to be generic for several types x-ray machines. Told contr he should disconnect power until evaluation was done. BCC 4-05-33(A) Equipment shall be listed as an assembly,450.13(B) transformer shall be readily accessible,400.5(A) st cord ampacity shall be per disconnect,400.8(1) cord shall not be used for fixed wiring,517.78shall apply for grounding ,517.13 shall apply for redundant gndg,250.118 shall apply for equipment gndg,110.2 equipment shall be acceptable only if approved
|