Inspections for the day of: Wednesday, January 11, 2006.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00885 INSP-Final Inspection1/10/20061/11/20061/11/2006 3:48:07 PMPPASS
Fire alarm is satisfactory, passed final inspection.
BLD05-02558 FIRE-Final Inspection1/11/20061/11/20061/11/2006 2:22:16 PMPPASS
Life safety passed inspection.
BLD05-02892 FIRE-Final Inspection1/11/20061/11/20061/11/2006 12:16:56 PMAPASS
Fire life safety finaled, inspection passed.
BLD05-02892 FIRE-Alarm Testing1/11/20061/11/20061/11/2006 12:14:53 PMAPASS
Duct smoke detector functioned correctly.
BLD05-02030 FIRE-Final Inspection1/11/20061/11/20061/11/2006 12:13:31 PMAPASS
Life safety is satisfactory.
BLD05-02030 FIRE-Alarm Testing1/11/20061/11/20061/11/2006 12:12:52 PMAPASS
HVAC duct smoke detector functioned properly.
FIR05-00841 INSP-Sprinkler Rough-in1/10/20061/11/20061/11/2006 12:07:53 PMAPART
Overhead rough-in is acceptable to cover pending corrections as noted on plans including overspaced head at kitchen, overspaced head at 2nd floor hall, install head at master bathroom as indicated, the backflow device installed is not as submitted (provide correct device or verify calcs are the same), tenting at cold cavity areas is satisfactory.