ELE06-02974
| Final | 1/10/2007 | 1/11/2007 | 1/11/2007 4:03:43 PM | P | PASS |
|
|
Phone #: ###-#### called about covers, ok to final
|
ELE06-02615
| Electrical Rough-In | 1/11/2007 | 1/11/2007 | 1/11/2007 3:55:29 PM | P | PART |
|
|
buster; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to cover sw outside wall with brick, told to call for other wall inspections
|
ELE06-01645
| Electrical Rough-In | 1/11/2007 | 1/11/2007 | 1/11/2007 3:18:06 PM | P | FAIL |
|
|
brian - call 30 min prior to inspection please; Phone #: ###-#### Internet Inspection Request from: Victoria Beall met owner, left corr notice, nec 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 210.52(D) bath recpts shall be on wall or partition adjacent to basin, 210.52(A) recpts shall be installed on bedroom wall, BCC no violations shall be retained
|
ELE06-02121
| Electrical Rough-In | 1/11/2007 | 1/11/2007 | 1/11/2007 3:08:06 PM | P | PASS |
|
|
lauren; Phone #: ###-#### Internet Inspection Request from: Victoria Beall corr made, ric ok
|
ELE07-00129
| Electrical Rough-In | 1/11/2007 | 1/11/2007 | 1/11/2007 2:26:46 PM | P | PASS |
|
|
roger ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ric ok, called , need to see new east walls
|
ELE06-02602
| Electrical Rough-In | 1/11/2007 | 1/11/2007 | 1/11/2007 1:20:08 PM | P | PASS |
|
|
ron - please call 1/2 hr prior to inspection ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith corr made, ric ok
|
ELE07-00131
| Final | 1/11/2007 | 1/11/2007 | 1/11/2007 10:29:34 AM | A | PASS |
|
|
ok to final
|
ELE07-00131
| Electrical Rough-In | 1/11/2007 | 1/11/2007 | 1/11/2007 10:24:59 AM | A | PASS |
|
|
called to add cover to open box
|
ELE07-00050
| Electrical Rough-In | 1/10/2007 | 1/11/2007 | 1/11/2007 10:24:00 AM | A | CANC |
|
|
READY FOR INSPECTION OF TRACK LIGHTING Phone #: ###-#### x0000 wrong address, wrong permit
|
ELE07-00008
| Electrical Rough-In | 1/10/2007 | 1/11/2007 | 1/11/2007 9:59:36 AM | A | FAIL |
|
|
jake - note cell# for lock box code ###-#### or ###-####; Phone #: ###-#### Internet Inspection Request from: Victoria Beall called contr, left corr notice, nec 300.4(A) edge of bored holes shall be 1 1/4" from face of framing members, 210.52(A)(1) no wall space shall be over 6' from recpt, 334.30 nm cable shall be strapped within 12" of box, 240.24(B) each occupant shall have access to all overcurrent devices for that occupancy
|
ELE07-00063
| Rough-In Permanent Service | 1/10/2007 | 1/11/2007 | 1/11/2007 8:42:48 AM | A | PASS |
|
|
daryl - unattached garage also ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ric ok both house and garage, need to see trench between two, p/s o/h n ok
|
ELE06-02364
| Final | 1/10/2007 | 1/11/2007 | 1/11/2007 8:39:59 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 1/10/2007 at 3:09:52 PM. Contact: ###-####. approval on listing ok, ok to final, signed occ card
|