Inspections for the day of: Thursday, January 11, 2007.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00762 INSP-Sprinkler Rough-in1/11/20071/11/20071/12/2007 2:22:43 PMPPART
OH fire sprinkler install is okay for cover at the areas where drop ceilings have been completed to date.
FIR06-00440 INSP-Final Inspection1/9/20071/11/20071/12/2007 10:38:20 AMAFAIL
Final pending correct wiring for power supply at the flow switch.
FIR06-00880 INSP-Sprinkler Rough-in1/10/20071/11/20071/11/2007 4:09:16 PMAPART
UG supply line is acceptable for cover pending the bury depth maintains the min. 4'6" after the existing lanscape burm is regraded.
FIR06-00644 INSP-Final Inspection1/10/20071/11/20071/11/2007 4:02:09 PMPFAIL
The hood suppression system failed to operate during testing, also advised contractor to call in related FA permit at at next inspection as both permits are issued to this same sub.
FIR06-00898 INSP-Final Inspection1/11/20071/11/20071/11/2007 3:07:01 PMPPART
BLD06-02377 FIRE-Final Inspection1/11/20071/11/20071/11/2007 3:04:53 PMPFAIL
Missing one exit sign, need to post max. occupant load sign, mount fire extinguishers as discussed, install closures at two locations, the project related fire alarm permit must be finaled prior to life safety final.
FIR06-00963 INSP-Final Inspection1/10/20071/11/20071/11/2007 3:02:34 PMAFAIL
Existing strobes at some locations are mounted below min. height allowed AFF, strobe notification devices in some areas are not in synchronization as required, need to lower two pull stations, a/v's at two locations are blocked by doors when in the open position, a/v's are overspaced at the SW corner, will check new nac batteries, modifications, as-built plans, and signal verification at next inspection.
BLD06-03210 FIRE-Final Inspection1/11/20071/11/20071/11/2007 10:31:55 AMPPASS
Fire life safety is acceptable, inspection passed.
FIR06-00875 INSP-Final Inspection1/11/20071/11/20071/11/2007 10:31:07 AMPPASS
Fire sprinkler permit finaled.
FIR06-00646 INSP-Alarm Testing1/10/20071/11/20071/11/2007 9:56:07 AMACANC
Forrest will 8:30 am work for you? Would you call me if that will not work. Thank you. Jason Gordon M2 Automation. Phone #: ###-#### Inspection cancelled from web by: Mike Timmerman
FIR06-00595 INSP-Alarm Testing1/10/20071/11/20071/11/2007 9:31:25 AMAPART
Inspection for the basement level audio/visual alarm notification functionality and coverage only completed today, noted file room coverage is lacking, still need to test manual pulls, relocated SD's, check EOL voltage.
BLD06-01831 FIRE-Final Inspection1/10/20071/11/20071/11/2007 9:23:25 AMAPASS
Required corrections have been verified for completion, fire life safety final inspection passed.
FIR06-00892 INSP-Final Inspection1/9/20071/11/20071/11/2007 9:22:22 AMAPASS
Fire alarm work is acceptable, permit finaled.
BLD06-03552 FIRE-Final Inspection1/10/20071/11/20071/11/2007 9:21:46 AMAFAIL
Missing fire extinguisher, need to provide additional emergency lighting at the east hall, the project related fire sprinkler permit must be finaled prior to life safety approval, noted some locations lacking proper sprinkler coverage or which are obstructed.
FIR06-00596 INSP-Final Inspection1/10/20071/11/20071/10/2007 1:35:31 PMPCANC
this is rafe''s cell. the inspection is for the 5th floor Phone #: ###-#### Inspection cancelled from web by: Terry Owsley