Inspections for the day of: Thursday, January 11, 2007.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MIS06-00247 FIR-Final1/11/20071/11/20071/11/2007 4:44:43 PMPPASS
Life safety passed.
BLD06-01466 FIRE-Final Inspection1/10/20071/11/20071/11/2007 4:44:02 PMPCANC
To be rescheduled since fire alarm is not ready
FIR06-00733 INSP-Final Inspection1/10/20071/11/20071/11/2007 2:40:28 PMPCANC
Per discussion with Troy this inspection will be rescheduled with the alarms and life safety
FIR05-00799 INSP-Final Inspection1/11/20071/11/20071/11/2007 2:29:51 PMPFAIL
All of the strobes are mounted too low. No testing performed.
MIS06-00343 FIR-Final1/10/20071/11/20071/11/2007 2:28:12 PMAPASS
Life safety finaled
FIR06-00758 INSP-Supply line flush1/5/20071/11/20071/11/2007 11:58:06 AMAPASS
Underground hydro test and flush passed.
FIR06-00977 INSP-Sprinkler Rough-in/Hydro1/10/20071/11/20071/11/2007 11:54:59 AMAPART
The first floor tenant area piping rough-in has passed. The piping below the stairs and into the elevator has not been installed yet. See the plans for the areason the second floor that can be covered.
FIR06-00623 INSP-Sprinkler Rough-in/Hydro1/10/20071/11/20071/11/2007 11:22:20 AMAFAIL
Could not get access into the building. Tried twice.
FIR05-00827 INSP-Sprinkler Rough-in1/10/20071/11/20071/11/2007 11:16:43 AMAPASS
See the city approved plans for the corridor and side room where the piping is ok to cover
FIR05-00693 INSP-Sprinkler Rough-in1/10/20071/11/20071/11/2007 11:15:57 AMAPASS
See the city approved plans for the single room where the piping is ok to cover
FIR06-00733 INSP-Sprinkler Rough-in/Hydro1/10/20071/11/20071/11/2007 8:40:44 AMAPASS
24 hour air test on the dry system and the forward flush passed.