Inspections for the day of: Friday, January 11, 2008.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE08-00061 Electrical Rough-In1/10/20081/11/20081/11/2008 4:06:22 PMPPASS
need ok to cover. Phone #: ###-#### Internet Inspection Request from: Randy Fletcher ric ok
ELE08-00089 Electrical Rough-In1/10/20081/11/20081/11/2008 3:07:12 PMPPASS
allen Note: cover up Phone #: ###-#### called contractor about panel clearance for final, ric ok
ELE07-03888 Final1/11/20081/11/20081/11/2008 2:15:08 PMPFAIL
ron - please call 1/2 hr prior to inspection Phone #: ###-#### met owner, nec corrections 210.8(A)(2) receptacles shall be gfci protected, 408.4 circuit directory shall be correct, 314.25 completed installations require box to be covered, 406.5 shall install receptacle faceplates
ELE07-04087 Permanent Service1/11/20081/11/20081/11/2008 1:14:57 PMPPASS
don Phone #: ###-#### p/s, o/h, n (rec), ok
ELE07-04134 Electrical Rough-In1/11/20081/11/20081/11/2008 12:47:02 PMPFAIL
don Phone #: ###-#### called, left correction notice, nec 330.30(B) mc cable shall be supported within 12" of box, 110.12(A) unused openings shall be closed in boxes, 300.14 at least 6" free conductor shall be left in box, BCC job id sticker shall be posted
ELE05-03636 DOC - Permit Expired1/11/20081/11/20081/11/2008 10:23:05 AMAPASS
ELE08-00057 Permanent Service1/10/20081/11/20081/11/2008 10:17:22 AMACANC
Need final on permanent service Phone #: ###-#### Internet Inspection Request from: Randy Fletcher see final
ELE08-00057 Final1/11/20081/11/20081/11/2008 10:04:57 AMAPASS
Need final on permanent service Phone #: ###-#### Internet Inspection Request from: Randy Fletcher ok to final
ELE08-00041 Final1/11/20081/11/20081/11/2008 9:37:00 AMPPASS
Tom wonnocot is the electrician @ ###-####, please provide inspection Phone #: ###-#### Internet Inspection Request from: gary batten see rip, ok to final
ELE08-00041 Rough-In Permanent Service1/11/20081/11/20081/11/2008 9:36:08 AMPPASS
Tom wonnocot is the electrician @ ###-####, please provide inspection Phone #: ###-#### Internet Inspection Request from: gary batten corrections made ric ok, p/s o/h rec ok
ELE07-03415 Final1/10/20081/11/20081/11/2008 8:58:04 AMAPASS
kenneth Phone #: ###-#### corrections made, ok to final