Inspections for the day of: Friday, January 11, 2008.
Number of inspections: 22
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00760 FIR-Aging Inspection1/11/20081/11/20081/15/2008 11:51:41 AM DONE
On site visit confirmed work has been completed, will need plans on site and permit requested for final inspection to close out this project.
FIR07-00039 INSP-Final Inspection1/10/20081/11/20081/14/2008 1:39:23 PMAFAIL
Need to replace one painted head at the entryway closet.
FIR07-00023 INSP-Final Inspection1/10/20081/11/20081/14/2008 1:37:19 PMAFAIL
One head at the master bedroom is obstructed by an adjacent light fixture, one missing escutcheon installed while on site.
FIR07-00149 INSP-Final Inspection1/10/20081/11/20081/14/2008 1:34:49 PMAPART
Final pending accurate as-built drawings.
FIR07-00150 INSP-Final Inspection1/10/20081/11/20081/14/2008 1:34:06 PMAPART
Okay for final pending accurate as-built plans.
FIR07-00037 INSP-Final Inspection1/10/20081/11/20081/14/2008 1:33:02 PMAFAIL
As-built drawings do not match the floor plan, one head has been deleted, one head at the master bedroom is obstructed by a surface mounted light fixture.
BLD08-00009 FIRE-Final Inspection1/11/20081/11/20081/14/2008 8:40:17 AMPPASS
All corrections made per last inspection. KR
FIR07-00913 INSP-Final Inspection1/11/20081/11/20081/11/2008 3:53:43 PMPFAIL
Blocked head at the storage room in the basement, need to replace one painted head at the sales floor, mixed temp heads at the west stairway next to the FACP.
BLD07-02015 FIRE-Final Inspection1/10/20081/11/20081/11/2008 3:51:50 PMAFAIL
Need to provide missing exit signs at three locations per plan annotations sheet E100, remove tape and paper covering at the FACP SD, need project related fire sprinkler and BLD shell permit finals.
BLD07-02761 FIRE-Final Inspection1/11/20081/11/20081/11/2008 2:20:57 PMPDEFR
kevin - fire life safety Phone #: ###-#### Rescheduled
FIR06-00365 INSP-Final Inspection1/10/20081/11/20081/11/2008 2:01:30 PMAFAIL
Coverage is obstructed by structural columns at five locations.
FIR07-00957 INSP-Final Inspection1/11/20081/11/20081/11/2008 1:39:26 PMPCANC
Overbooked.
FIR06-00587 INSP-Sprinkler Rough-in1/10/20081/11/20081/11/2008 1:36:58 PMANH
No access provided to complete inspection.
BLD07-01578 FIRE-Final Inspection1/10/20081/11/20081/11/2008 1:15:47 PMAPASS
Fire life safety inspection completed satisfactory, inspection passed.
FIR07-00695 INSP-Final Inspection1/10/20081/11/20081/11/2008 11:57:42 AMACANC
Overbooked.
FIR07-00962 INSP-Final Inspection1/10/20081/11/20081/11/2008 11:45:51 AMPCANC
Overbooked.
FIR07-00039 INSP-Final Inspection1/10/20081/11/20081/11/2008 11:44:16 AMPCANC
Duplicate inspection request.
FIR08-00012 INSP-Sprinkler Rough-in1/10/20081/11/20081/11/2008 11:43:01 AMAPART
Demo portion only of this permit completed to date, initialed on approved plan set.
BLD07-03235 FIRE-Final Inspection1/11/20081/11/20081/11/2008 11:24:07 AMPCANC
Overbooked.
FIR08-00004 INSP-Final Inspection1/10/20081/11/20081/11/2008 11:12:48 AMAPASS
Fire sprinkler scope of permit work completed satisfactory, permit finaled.
FIR07-01026 INSP-Sprinkler Rough-in1/9/20081/11/20081/11/2008 11:11:48 AMAPART
OH rough-in is approved for cover at the drop ceiling areas- see approved plans for annotations.
FIR07-00976 INSP-Final Inspection1/10/20081/11/20081/11/2008 11:10:40 AMAPASS
UG fire supply line permit finaled.