ELE09-01000
| ELE-Aging Inspection | 1/11/2010 | 1/11/2010 | 1/14/2010 12:02:26 PM | | DONE |
|
|
no activity, see doc expire
|
ELE08-01303
| ELE-Aging Inspection | 1/11/2010 | 1/11/2010 | 1/12/2010 9:19:32 AM | | DONE |
|
|
no activity, see doc expire
|
ELE10-00050
| Rough-In Permanent Service | 1/11/2010 | 1/11/2010 | 1/11/2010 3:58:20 PM | P | CANC |
|
|
Steve Phone #: ###-#### wrong type request see p/s
|
ELE10-00050
| Permanent Service | 1/11/2010 | 1/11/2010 | 1/11/2010 3:58:00 PM | P | PASS |
|
|
Steve Phone #: ###-#### p/s u/g n ok
|
ELE10-00050
| Electrical Rough-In | 1/11/2010 | 1/11/2010 | 1/11/2010 3:56:51 PM | P | FAIL |
|
|
Steve Phone #: ###-#### called, left message, left correction notice,NEC 300.4 edge of bored holes shall be 1 1/4" from edge of framing members or cable shall be protected be steel plates, 210.52(A) shall install receptacles such that no point along wall line is over 6' from an outlet, NOTE : shall affix box in kitchen, terminate nm cable in kitchen ceiling, adress either 3rd floor unfinished or not
|
ELE09-02295
| Electrical Rough-In | 1/11/2010 | 1/11/2010 | 1/11/2010 3:51:59 PM | P | PART |
|
|
Ceiling inspection Dan ###-#### ok to cover ceilings, left correction notice for rootop, NEC 210.63 shall provide weather proof and gfci receptacle within 25' of exhaust fan, BCC no violations shall be retained, no esc this project
|
ELE10-00044
| Conference | 1/11/2010 | 1/11/2010 | 1/11/2010 3:26:57 PM | P | DONE |
|
|
Mariana please call 30 min before going out Phone #: ###-#### reviewed service change electrical requirements, when to call for inspection, told owner needs to get structural (bld) and plumbing permits, no esc this project
|
ELE09-02260
| Conference | 1/8/2010 | 1/11/2010 | 1/11/2010 3:24:43 PM | A | DONE |
|
|
Tony Phone #: ###-#### met contractor with 414, will check out motor data sheets with ul
|
ELE09-01596
| Final | 1/10/2010 | 1/11/2010 | 1/11/2010 2:48:57 PM | P | PASS |
|
|
Steve Phone #: ###-#### ok to final
|
ELE10-00049
| Permanent Service | 1/11/2010 | 1/11/2010 | 1/11/2010 12:56:43 PM | P | FAIL |
|
|
Allan please call for access code Phone #: ###-#### called, contractor has to bring service up to code, BCC no violations shall be retained
|
GCE09-00049
| GCE-Final | 1/8/2010 | 1/11/2010 | 1/11/2010 12:01:30 PM | A | FAIL |
|
|
Contact # ###-####or Tim @ ###-#### called, left correction notice, NEC 250.24(A)(1) gec shall be terminated on terminal to which grounded conductor is terminated, 312.5 all conductors entering enclosure shall have abrasion protection, 250.24(A)(5) load side service disconnect grounded conductor shall not be connected to equipment grounding conductor, 250.96 non-conductive paint shall be removed at contact points, told contractor to ask for p/s inspection, no esc this project
|
ELE09-02363
| Final | 1/8/2010 | 1/11/2010 | 1/11/2010 10:07:37 AM | A | PASS |
|
|
Daryl Phone #: ###-#### ok to final
|
GCE10-00002
| GCE-Final | 1/8/2010 | 1/11/2010 | 1/11/2010 9:02:04 AM | A | PASS |
|
|
Contact Nandy @ ###-####Home owner Mary@ ###-#### ok to final, no esc this project
|
ELE10-00044
| Conference | 1/8/2010 | 1/11/2010 | 1/11/2010 8:29:56 AM | A | NH |
|
|
###-#### John called, left message, left card, no esc this project
|
ELE09-02029
| Final | 1/8/2010 | 1/11/2010 | 1/11/2010 8:11:41 AM | A | PASS |
|
|
Bob, this is for several clean room tools in Fab 4. Phone #: ###-#### Internet Inspection Request from: Eric Landberg ok to final, no esc this project
|
ELE09-01162
| Final | 1/8/2010 | 1/11/2010 | 1/11/2010 8:01:28 AM | A | PASS |
|
|
Bob, this is my blanket permit for building 24. Phone #: ###-#### Internet Inspection Request from: Eric Landberg ok to final, no esc this project
|