Inspections for the day of: Monday, January 11, 2010.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE09-01000 ELE-Aging Inspection1/11/20101/11/20101/14/2010 12:02:26 PM DONE
no activity, see doc expire
ELE08-01303 ELE-Aging Inspection1/11/20101/11/20101/12/2010 9:19:32 AM DONE
no activity, see doc expire
ELE10-00050 Rough-In Permanent Service1/11/20101/11/20101/11/2010 3:58:20 PMPCANC
Steve Phone #: ###-#### wrong type request see p/s
ELE10-00050 Permanent Service1/11/20101/11/20101/11/2010 3:58:00 PMPPASS
Steve Phone #: ###-#### p/s u/g n ok
ELE10-00050 Electrical Rough-In1/11/20101/11/20101/11/2010 3:56:51 PMPFAIL
Steve Phone #: ###-#### called, left message, left correction notice,NEC 300.4 edge of bored holes shall be 1 1/4" from edge of framing members or cable shall be protected be steel plates, 210.52(A) shall install receptacles such that no point along wall line is over 6' from an outlet, NOTE : shall affix box in kitchen, terminate nm cable in kitchen ceiling, adress either 3rd floor unfinished or not
ELE09-02295 Electrical Rough-In1/11/20101/11/20101/11/2010 3:51:59 PMPPART
Ceiling inspection Dan ###-#### ok to cover ceilings, left correction notice for rootop, NEC 210.63 shall provide weather proof and gfci receptacle within 25' of exhaust fan, BCC no violations shall be retained, no esc this project
ELE10-00044 Conference1/11/20101/11/20101/11/2010 3:26:57 PMPDONE
Mariana please call 30 min before going out Phone #: ###-#### reviewed service change electrical requirements, when to call for inspection, told owner needs to get structural (bld) and plumbing permits, no esc this project
ELE09-02260 Conference1/8/20101/11/20101/11/2010 3:24:43 PMADONE
Tony Phone #: ###-#### met contractor with 414, will check out motor data sheets with ul
ELE09-01596 Final1/10/20101/11/20101/11/2010 2:48:57 PMPPASS
Steve Phone #: ###-#### ok to final
ELE10-00049 Permanent Service1/11/20101/11/20101/11/2010 12:56:43 PMPFAIL
Allan please call for access code Phone #: ###-#### called, contractor has to bring service up to code, BCC no violations shall be retained
GCE09-00049 GCE-Final1/8/20101/11/20101/11/2010 12:01:30 PMAFAIL
Contact # ###-####or Tim @ ###-#### called, left correction notice, NEC 250.24(A)(1) gec shall be terminated on terminal to which grounded conductor is terminated, 312.5 all conductors entering enclosure shall have abrasion protection, 250.24(A)(5) load side service disconnect grounded conductor shall not be connected to equipment grounding conductor, 250.96 non-conductive paint shall be removed at contact points, told contractor to ask for p/s inspection, no esc this project
ELE09-02363 Final1/8/20101/11/20101/11/2010 10:07:37 AMAPASS
Daryl Phone #: ###-#### ok to final
GCE10-00002 GCE-Final1/8/20101/11/20101/11/2010 9:02:04 AMAPASS
Contact Nandy @ ###-####Home owner Mary@ ###-#### ok to final, no esc this project
ELE10-00044 Conference1/8/20101/11/20101/11/2010 8:29:56 AMANH
###-#### John called, left message, left card, no esc this project
ELE09-02029 Final1/8/20101/11/20101/11/2010 8:11:41 AMAPASS
Bob, this is for several clean room tools in Fab 4. Phone #: ###-#### Internet Inspection Request from: Eric Landberg ok to final, no esc this project
ELE09-01162 Final1/8/20101/11/20101/11/2010 8:01:28 AMAPASS
Bob, this is my blanket permit for building 24. Phone #: ###-#### Internet Inspection Request from: Eric Landberg ok to final, no esc this project