BLD10-01205
| FIRE-Final Inspection | 1/6/2011 | 1/7/2011 | | A | |
|
|
301
|
FIR10-00069
| INSP-Final Inspection | 1/10/2011 | 1/11/2011 | 1/11/2011 4:49:09 PM | P | PASS |
|
|
Fire alarm permit finaled. Inspection passed.
|
FIR10-00221
| FIR-Aging Inspection | 1/11/2011 | 1/11/2011 | 1/11/2011 4:03:31 PM | | PASS |
|
|
Scope of demo permit work is finished.
|
FIR10-00180
| FIR-Aging Inspection | 1/11/2011 | 1/11/2011 | 1/11/2011 4:01:13 PM | | PEND |
|
|
Ref. correction notice
|
FIR10-00251
| FIR-Aging Inspection | 1/11/2011 | 1/11/2011 | 1/11/2011 3:59:48 PM | | DONE |
|
|
|
FIR10-00588
| INSP-Sprinkler Rough-in | 1/10/2011 | 1/11/2011 | 1/11/2011 3:53:05 PM | A | PART |
|
|
Overhead fire sprinkler system modifications at the new tenant remodel are approved for cover. *Notified general contractor to maintain ceiling at the adjacent existing tenant space where modified to accomodate new wall construction. Ref. IFC 2006 901.4 and NFPA 13 2007 8.1(3)..
|
FIR10-00652
| INSP-Final Inspection | 1/11/2011 | 1/11/2011 | 1/11/2011 3:47:16 PM | P | PASS |
|
|
Scope of permit work verified for completion- ceiling tile and escutcheons at the new acoustic grid are finished. Fire sprinkler permit finaled.
|
FIR10-00540
| INSP-Sprinkler Rough-in | 1/11/2011 | 1/11/2011 | 1/11/2011 3:42:58 PM | P | PART |
|
|
Inspection completed to verify retainer straps at beam clamps for the first floor 3" main hangers only.
|
FIR11-00007
| INSP-Final Inspection | 1/11/2011 | 1/11/2011 | 1/11/2011 3:34:16 PM | P | PASS |
|
|
Fire sprinkler permit okay for final.
|
FIR11-00003
| INSP-Final Inspection | 1/11/2011 | 1/11/2011 | 1/11/2011 3:26:45 PM | P | PART |
|
|
Corrections per last notice at the RDG tenant space verified for completion.
|
FIR10-00616
| INSP-Sprinkler Rough-in | 1/10/2011 | 1/11/2011 | 1/11/2011 1:32:09 PM | A | PART |
|
|
Okay to cover grid ceiling areas at rooms below the mezzanine including upright protection below the stairs.
|
BLD10-02129
| FIRE-Conference | 1/10/2011 | 1/11/2011 | 1/11/2011 11:36:32 AM | A | DEFR |
|
|
Intended request date 1/12
|
FIR11-00007
| INSP-Sprinkler Rough-in | 1/10/2011 | 1/11/2011 | 1/11/2011 11:23:23 AM | A | PART |
|
|
Overhead rough-in passed inspection.
|
BLD10-02344
| FIRE-Conference | 1/10/2011 | 1/11/2011 | 1/11/2011 11:21:52 AM | A | DONE |
|
|
Regarding occupant load, exit signs and emergency lighting.
|
BLD10-02759
| FIRE-Final Inspection | 1/10/2011 | 1/11/2011 | 1/11/2011 10:31:21 AM | A | NR |
|
|
Fire life safety final pending fire sprinkler system work in the tenant space- corrections included.
|