FIR11-00365
| INSP-Sprinkler Rough-in | 1/10/2012 | 1/11/2012 | 1/11/2012 5:19:51 PM | P | FAIL |
|
|
Inspection for intended for system # 8- contractor missing approved plans on site. Completed initial walk of this area and noted some items including two mixed temp. heads, blocked uprights at unistrut hangers, overspaced coverage adjacent to the west plenum wall, a vestibule without coverage, obstruction >4'. Need stamped plans for verification installation meets design, bracing locations, etc.
|
FIR11-00301
| INSP-Supply line flush | 1/10/2012 | 1/11/2012 | 1/11/2012 5:05:20 PM | P | NR |
|
|
Contractor unable to complete supply line flushing at the NW riser due to jobsite conditions.
|
BLD11-01901
| FIRE-Final Inspection | 1/11/2012 | 1/11/2012 | 1/11/2012 4:59:40 PM | A | PEND |
|
|
Final pending project related fire alarm panel repair work.
|
FIR11-00676
| INSP-Final Inspection | 1/10/2012 | 1/11/2012 | 1/11/2012 4:59:01 PM | A | NR |
|
|
Panel indicates trouble with phone line #2, comm. fail.
|
BLD11-02881
| FIRE-Final Inspection | 1/9/2012 | 1/11/2012 | 1/11/2012 11:53:41 AM | A | PASS |
|
|
Fire life safety inspection completed satisfactory.
|
FIR11-00673
| INSP-Final Inspection | 1/11/2012 | 1/11/2012 | 1/11/2012 11:52:55 AM | A | PASS |
|
|
Final inspection passed, scope of work complete. Fire sprinkler permit finaled.
|