FIR12-00557
| INSP-Final Inspection | 1/11/2013 | 1/11/2013 | 1/11/2013 3:50:52 PM | P | FAIL |
|
|
Todays inspection was just verification that the notification circuits and devices functioned.They were out of sync but were repaired. EOL voltage was verified as ok. Candellas were adjusted in several locations due to spacing issues. Spacing was verified on only the low ceiling areas. The high ceilings will need to be checked later. As-builts will be required showing the revised circuits and candellas and additional devices.
|
BLD13-00029
| FIRE-Final Inspection | 1/10/2013 | 1/11/2013 | 1/11/2013 3:46:42 PM | A | PART |
|
|
A temporary occupancy is being given with Romeo's permission until the fire sprinkler issues have been addressed. A letter has been provided that states a fire sprinkler contractor has been hired to perform the work.
|
FIR12-00661
| INSP-Sprinkler Rough-in/Hydro | 1/11/2013 | 1/11/2013 | 1/11/2013 2:51:18 PM | P | PART |
|
|
The sprinkler rough in passed but the second floor piping can not be covered until the tenting has been installed and approved. The hydro tests are partially passed. Neither system was sectioned off and one guage gained pressure and the other lost. The fitter marked the guages. Another hydro test will be required once the building is closed up from the elements.
|
FIR12-00728
| INSP-Sprinkler Rough-in | 1/11/2013 | 1/11/2013 | 1/11/2013 1:51:22 PM | P | PASS |
|
|
Rough-in passed. Sprinkler piping is ok to cover.
|
FIR12-00722
| INSP-Final Inspection | 1/11/2013 | 1/11/2013 | 1/11/2013 1:38:08 PM | P | PASS |
|
|
Permit finaled
|
BLD12-01994
| FIRE-Final Inspection | 1/10/2013 | 1/11/2013 | 1/11/2013 11:33:50 AM | A | FAIL |
|
|
Life saftey will be ok to final when a fire alarm permit has been issed/finaled to extend the fire alarm sytem into the new restroom.. The manual pull station has already been relocated.
|
FIR12-00727
| INSP-Final Inspection | 1/10/2013 | 1/11/2013 | 1/11/2013 10:52:25 AM | A | FAIL |
|
|
Rough-in passed. Sprinkler piping can be covered.
|
BLD11-01635
| FIRE-Final Inspection | 1/10/2013 | 1/11/2013 | 1/11/2013 9:35:51 AM | A | FAIL |
|
|
Provide fire extinguishers as discussed.
|