Inspections for the day of: Friday, January 11, 2013.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR12-00557 INSP-Final Inspection1/11/20131/11/20131/11/2013 3:50:52 PMPFAIL
Todays inspection was just verification that the notification circuits and devices functioned.They were out of sync but were repaired. EOL voltage was verified as ok. Candellas were adjusted in several locations due to spacing issues. Spacing was verified on only the low ceiling areas. The high ceilings will need to be checked later. As-builts will be required showing the revised circuits and candellas and additional devices.
BLD13-00029 FIRE-Final Inspection1/10/20131/11/20131/11/2013 3:46:42 PMAPART
A temporary occupancy is being given with Romeo's permission until the fire sprinkler issues have been addressed. A letter has been provided that states a fire sprinkler contractor has been hired to perform the work.
FIR12-00661 INSP-Sprinkler Rough-in/Hydro1/11/20131/11/20131/11/2013 2:51:18 PMPPART
The sprinkler rough in passed but the second floor piping can not be covered until the tenting has been installed and approved. The hydro tests are partially passed. Neither system was sectioned off and one guage gained pressure and the other lost. The fitter marked the guages. Another hydro test will be required once the building is closed up from the elements.
FIR12-00728 INSP-Sprinkler Rough-in1/11/20131/11/20131/11/2013 1:51:22 PMPPASS
Rough-in passed. Sprinkler piping is ok to cover.
FIR12-00722 INSP-Final Inspection1/11/20131/11/20131/11/2013 1:38:08 PMPPASS
Permit finaled
BLD12-01994 FIRE-Final Inspection1/10/20131/11/20131/11/2013 11:33:50 AMAFAIL
Life saftey will be ok to final when a fire alarm permit has been issed/finaled to extend the fire alarm sytem into the new restroom.. The manual pull station has already been relocated.
FIR12-00727 INSP-Final Inspection1/10/20131/11/20131/11/2013 10:52:25 AMAFAIL
Rough-in passed. Sprinkler piping can be covered.
BLD11-01635 FIRE-Final Inspection1/10/20131/11/20131/11/2013 9:35:51 AMAFAIL
Provide fire extinguishers as discussed.